5 Control system
SMGB0070 rev. 1 - 08/2011
151
5
Maximum set-point selected by Installer
In order to avoid excessively hot water in the tank, there is an additional function that allows the installer to set a maximum
temperature.
CODE
REF
Description
Default Value
Range
Steps
Units
3-122
T
DHWMAX
DHW maximum set-point Tº
55
40~70
1
ºC
N O T E
Antilegionella function has no effect.
High demand mode differential (T
DHWON
)
Sanitary Water Heater will start when following conditions are met:
•
System is set to HIGH DEMAND Mode
Other functions may cause Sanitary Water Heater to start regardless of this control. For example, Sanitary Water Heater
may be started by Electric Heater Wait time.
CODE
REF
Description
Default Value
Range
Steps
Units
3-023
T
DHWON
DHW differential
6
2~15
1
ºC
Time
T
DHW
T
DHWON
T
DHWS
T (ºC)
T
DHW
: Water temperature in DHW (ºC) (by THM
DHW
sensor)
T
DHWS
: Water temperature setting in DHW (ºC)
T
DHWON
: Domestic hot water differential (temperature drop that starts DHW)
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......