12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
408
Fault diagnosis procedure
Fault diagnosis of DC fan motor. About fan motor fault diagnosis:
When ISPM/DIP-IPM is faulty and alarm 53 appears, the fan motor may also be damaged. After replacing the new ISPM/
DIP-IPM, ISPM/DIP-IPM will be damaged again if it operates with a damaged fan motor. Check also if the fan motor is not
damaged when IPM/DIP-IPM is replaced.
C A U T I O N
• Turn OFF main power before start working.
• Working and checking with the power ON may disturb correct diagnosis and may result in failure.
Models with DC motor(s)
Nº of motors
RAS-2HVRN2
1 Piece
RAS-3HVRNME-AF
RAS-(4-10)H(V)RNME-AF
2 Pieces
RAS-(8/10)HRNME-AF
Procedure in case of error diagnosis
1
Remove fan motor connectors from the control PCB, ISPM or DIP-IPM and turn the fan motor shaft by hand.
Normal
Fan motor shaft turns smoothly
Faulty
No continuous rotary torque movement felt when turning the motor by hand. This occurs because the
internal magnet of the fan motor breaks the movement when the internal electronic circuit of the fan
motor has a short-circuit fault.
2
Measure the fan motor resistance:
Measurement procedure
1
Remove the fan motor connector from the control PCB, ISPM or DIP-IPM.
2
Connect the black test lead of the tester to the black wire pin of the fan motor connector.
3
Connect the red test lead to the wire connector pin to be checked.
Results
Normal
Observed values will be close to the normal values in the table below.
Faulty
Obbserved values will be deviated from the normal values in the table below. (Generally, an open-
circuit fault shows ∞, and a short-circuit fault shows several Ω - kΩ).
Internal electronic circuit fault of the fan motor including short-circuit and breakage can be checked.
Model
Motor model
Wire color for checking (Normal value)
Red-black
White-black
Yellow-black
Blue-black
RAS-2HVRN2
FPD10U4OS-902 or
DAJ12-55V71
13.5 - 14.4kΩ
1MΩ or greater
225-226kΩ
1MΩ or greater
RAS-4H(V)RNME-AF (upper)
RAS-(4-6)H(V)RNME-AF (lower)
SIC-65FV-D840-1
1MΩ or greater
26-50kΩ
168-312kΩ
1MΩ or greater
RAS-3HVRNME-AF
RAS-(5/6)HVRNME-AF (upper)
SIC-68FV-D851-7
1MΩ or greater
42-78kΩ
168-312kΩ
1MΩ or greater
RAS-(8/10)HRNME-AF
SIC-81FV-D8138-1
1MΩ or greater
42 - 78kΩ
168-312kΩ
1MΩ or greater
Values are shown for referential purpose. While actual values may vary depending on the type of the tester, any tester can
be used to determine any short-circuit or breakage based on ∞ or several Ω or 0 Ω or ∞.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......