12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
390
Alarm code
72
Thermostat Heater Alarm
•
The alarm code is displayed on the LCD User interface.
•
The alarm code is displayed on the seven segments of the indoor unit PCB.
•
This alarm code is displayed when electrical heater’s thermal protection is open (>75ºC).
Reset the thermal
protector by
pressing reset
button
Is the electri-
cal heater
thermostat (THe)
open?
Check the reset button on
the thermal protector. If
button is ON a pre-set (and
there is continuity between
terminals), but the Electrical
Heater continues OFF.
Yes
No
Check Electrical
Heater thermal
fuse
Yes
Has the
Thermal fuse
blown?
No
Have the
Electrical fuses
(EF1/2/3) blown?
Contact your local dealer
No
Yes
Contact your local dealer
Yes
Replace fuses
Alarm control procedure:
-
Switch OFF Outdoor and Indoor Units
-
Electrical Heater Disabled
-
Water pumps continue running up to water <55ºC.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......