12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
404
Activating condition of protection control code
For following the conditions as the temperature change, etc., the control of frequency, etc. is performed to prevent the
abnormal conditions by the protection control. The activating conditions of protection control are shown in the table below.
Code
Protection control
Activating condition
Remarks
P0
Low-pressure ratio control at
cooling operation
Compression ratio ε < 2.2
=> frequency increase
ε = (Pd+0.1)/(Ps+0.1)
P1
High-pressure ratio control at
heating operation
Compression ratio ε > 7.5
=> frequency decrease
ε = (Pd+0.1)/(Ps+0.1)
P2
High-pressure increase protection
High pressure switch for control is activated
=> frequency decrease
P3
Over current protection
Inverter output current > (*1)A
=> frequency decrease
P4
DipIPM, ISPM or IPM temperature
increase protection
Inverter fin temperature
RAS-(4-10)HRNME-AF > 100 ºC
RAS-(3-6)HVRNME > 80 ºC
=> Frequency decrease
P5
Discharge gas temperature
increase protection
Temperature at the top of compressor is high
=> frequency decrease
Temperature at the top of compressor > 107ºC
=> indicate P5
P6
Frost formation protection
TL ≤ 2ºC Over 3 minutes
=> Frequency decrease
TL: liquid piping, temperature of
indoor unit
P9
Unbalance power source detecting Inverter output current > 13A (380A)
=> frequency decrease
PA
Current demand control
Inverter output current > (*2)A
=> frequency decrease
In case of demand control setting
Pb
Low-pressure decrease protection Low pressure switch for control is activated
=> frequency decrease
PC
Cold draft protection
TO ≤ 10ºC and ε ≥ 2.6 => frequency decrease
ε = (Pd+0.1)/(Ps+0.1)
TO: outlet temperature of indoor unit
P7
Inverter retry
Automatic stoppage of transistor module, acti-
vation of electronic thermal or abnormal current
sensor
When activating 3 times in 30 minu-
tes, “48”, “51”, “53” or “54” alarm is
indicated.
P8
Inverter retry
Insufficient/excessive voltage at inverter
Circuit or PCB connector part
When activating 3 times in 30 minu-
tes, “06” or “55” alarm is indicated.
N O T E S
• During protection control (except during alarm stoppage), the protection control code is indicated.
• The protection control code is indicated during protection control and turns off when canceling the protection
control.
• After retry control, the condition of monitoring is continued for 30 minutes.
• The maximum value (*1) and (*2) are as follows:
(*1)
HP
380 – 415V
220 – 240V
4
5
3
4
5
Current (A)
8.0
12.0
16.0 16.0 24.0
(*2)
HP
Demand
setting
380 – 415V
220 – 240V
4
5
3
4
5
Current
(A)
100%
4.0
5.5
11.5 13.0 17.0
75%
3.0
4.0
8.5
10.0 13.0
50%
2.0
2.0
5.5
6.5
8.5
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......