12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
329
12
Alarm
code
Retry
stop
code
Origin
Detail of abnormality
Main cause
35
-
Outdoor Indoor unit number setting error
Indoor units with the same number in a refrigerant piping
system
38
-
Outdoor Outdoor protection detection circuit abnormality
Outdoor PCB abnormality, error in wiring to outdoor PCB
41
-
Outdoor Cooling overload
Outdoor heat exchanger clogging/short circuit, broken
outdoor fan motor
42
-
Outdoor Heating overload
Outdoor heat exchanger clogging/short circuit, expansion
valve close-locked
47
15
Outdoor Suction pressure decrease prevention activated
Shortage or leakage of refrigerant, piping clogging,
expansion valve close-locked, fan motor locked
51
17
Outdoor Inverter current sensor abnormality
Error in CT wiring, outdoor PCB abnormality, inverter PCB
abnormality
48
17
Outdoor Overload operation protection activation
Cycle abnormality, inverter PCB abnormality, DM abnor-
mality, heat exchanger clogging, etc.
53
17
Outdoor Inverter module error
Compressor, ISPM abnormality, heat exchanger clogging,
etc.
54
17
Outdoor
Inverter fin temperature abnormality
Fin thermistor abnormality, heat exchanger clogging, fan
motor abnormality
55
18
Outdoor Inverter non-operation
Inverter not operating or broken
59
-
Outdoor
Inverter fin temperature thermistor abnormality
Loose, disconnected, broken or short-circuited connector
b1
-
Outdoor Error in address/refrigerant system setting
Address/refrigerant system setting over 64
EE
-
Outdoor Compressor factor alarm
Alarm to notify damage to compressor occurs 3 times
within 6 hours
70
P-70
Indoor Hydraulic alarm
Water pressure or water flow is not detected in the
hydraulic cycle
71
-
Indoor
Water pump feedback
72
-
Indoor Thermostat heater alarm
High temperature is detected in electric heater T>75ºC
73
-
Indoor Mixing overheating limit protection for mixed
circuit.
Circuit 2 supply temperature > target tempe offset
74
P-74
Indoor Unit overheating limit protection
Two > Tmax +5K
75
-
Indoor Freeze protection by cold water inlet, outlet
temperature detection
76
-
Indoor Freeze protection stop by indoor liquid tempera-
ture thermistor
Tl or Tg < -20ºC for 30 seconds (Only heating mode)
77
-
Indoor Opentherm communication failure
No Opentherm communication for a continuous period of
1 minute.
78
-
Indoor RF Communication failure
No communication for 1 hour with one or two RF recei-
vers which are bound to the RF-Bridge.
79
-
Indoor
-outdoor Unit capacity setting error
No concordance between indoor and outdoor unit capa-
cities
80
-
Indoor-
LCD
LCD H-link transmission error
No H-link communication for a continuous period of 1 mi
-
nute between indoor and LCD user control by connection
wiring (breaking, wiring error, etc.)
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......