Chapter Five PLC Function Code
35
V
o
lume
I Programming
TIMER = Setting time
ACT
W
Fig. 5-12-2
Parameter:
TIMER: Fix the timer number, it is indicates by xxx, xxx is numbers from 0 to 127.
Table 5-12-1 (Timer accuracy)
Timer
accuracy
Setting No.
Timer range setting
Error range
8ms
0
From 8ms to 524.280s
Scan period from 0 to the 1
st
level program
48ms 1
From
48ms
to
31.456min
Scan period from 0 to the 1
st
level program
1s
2
From 1s to 546 min
Scan period from 0 to the 1
st
level program
10s
3
From 10s to 182 h
Scan period from 0 to the 1
st
level program
1min
4
From 1min to 65535min
From 0 to 1s
1ms
5
From 1ms to 65.4s
Scan period from 0 to the 1
st
level program
Presetting time
The time setting of the fixed timer, its numerical range is: 0~65535.
Output
W : Coil output. W=1, it reaches to the presetting. W=0, it does not reach.
Note:
As for the sequence of the timer, the system may check its range automatically, if the repeated sequence or
out of the range, the system may alarm. The presetting time in timer is solidified in the ROM along with the
ladder diagram, so, the time of the timer only can be changed by modifying the ladder diagram file.
5.13 TMRC (TIMER)
Function
Delay conducting timer
Format
TMRC
ACT
Timer
accuracy
Timer
number
(
W
)
Fig. 5-13-1
Controllable condition
ACT
=
0, Close the timer