Appendix I Ladder Diagram Usage Guide of GSK218mc Series with Cone Type Tool-Magazine
261
Appendix
Troubleshooting: Set the K010.6 to 0.
(Refer to the details operation: Section Three The Usage and Maintenance of the GSK218MC
Series with Cone Tool-magazine)
Alarm information: 1244 Tool-change abnormally stops, ensure the tool magazine is normal
(A005.4)
Fault reason: Tool magazine is being automatically performed the tool-change. Tool-change stops or
it can not detect that the tool magazine is not at the retraction position when starting
the system when the abnormality occurs, and then the alarm generates. This alarm is
only prompted that the operator tool magazine and the tool number on the spindle
may disorder. The tool magazine may still abnormal after cleaning this alarm, it is
better to reset the tool magazine and the tool number on the spindle. (Refer to the
details operation: Section Three The Usage and Maintenance of the GSK218MC
Series with Cone Tool-magazine).
Troubleshooting: 1. Immediately clear this alarm by “Reset” button.
2. Readjust the tool magazine and confirm the tool number on the spindle is
consistent, which includes the tool magazine returning to the retraction position,
spindle on the clamping state, as well, the current tool case is consistent with
the current value of the CTR100, the tool number on the spindle is consistent
with the D245 and ensure that there is no tool on the spindle when the value of
the D245 is set to 0.
Alarm information: 1245 There is code tool number in the tool table or code tool number repeated
(A005.5)
Fault reason: There is no specified tool number from the T code in tool table (D001-D099) or the tool
number specified from T code is repeated in the tool table.
Troubleshooting: Modify the tool number value in the tool table.
Alarm information: 1246 Fail to perform the infeed because it is not in the tool-change position
(A005.6)
Fault reason: Tool magazine infeed motion is performed when Z axis is not at the tool-change
position.
Troubleshooting: Perform the G91 G30 Z0 code so that the Z axis returns to the tool-change
position.
Alarm information: 1247 Tool magazine can not perform the infeed because the spindle is under