Appendix II Laddar Diagram Use Guide of GSK218mc Series Matching with Disc Tool Magazine
293
Appendix
Alarm information: 1212 Excessive low of the pressure grease (A001.4)
Fault reason: User self-defined
Troubleshooting:
Alarm information: 1213 Machine does not ready (A001.5)
Fault reason: User self-defined
Troubleshooting:
Alarm information: 1214 Spindle shifting abnormal, fail to rotate (A001.6)
Fault reason: Detect the spindle shift abnormality when the spindle is performed the rotation code.
Troubleshooting: The gear I in-position detection switch (X004.1) does not close within the setting
time of the T0021 when spindle changes the gear I (that is, Y3.4=1); adjust the
time of the T0021 or check whether the X004.1 is closed. The gear I in-position
detection switch (X004.2) does not close within the setting time of the T0022
when spindle changes the gear II (that is, Y3.5=1); adjust the T0022 time or check
whether the X004.2 is closed. The gear I in-position detection switch (X004.3)
does not close within the T0023 setting time when spindle changes the gear III
(that is 3.6=1); adjust the T0023 time or check whether the X004.3 is closed.
Alarm information: 1215 Firstly perform the T code before executing the M06 code (A001.7)
Fault reason: Fail to perform the enabled T code when executing the M06 code.
Troubleshooting: Perform the M06 code after executing the enabled T code.
Alarm information:1216 Fail to rotate the spindle in the tool releasing state (A002.0)
Fault reason: Perform the spindle rotation code when the tool is on the releasing state. For example:
Press the spindle positive, negative, JOG and positioning in the manual mode or the
spindle will be rotated by performing the M03, M04 and M19 in Auto state.
Troubleshooting: Press the “tool-clamping/tool-releasing” button to the tool-clamping state in the
manual state (that is: Y0.2=0); check whether the state of the tool-clamping
inspection switch (X2.6) is 1, if it does, this alarm will not generate by rotating the
spindle.
Alarm information: 1217 Fail to release the tool when spindle rotates (A002.1)
Fault reason: The tool-releasing code is performed when the spindle is on the rotation state.
Troubleshooting: Perform the tool-releasing code to avoid this alarm when the spindle is on the
stopping state.