GE Power Management
745 Transformer Management Relay
5-85
5 SETPOINTS
5.7 S5 OUTPUTS
5
5.7.5 TRACE MEMORY
Trace memory is the oscillography feature of the 745. All system inputs are synchronously digitized at a sam-
pling rate of 64 times a power cycle. Upon occurrence of a user-defined trigger condition, the 16 cycles of oscil-
lographic waveforms are captured into trace memory. The trigger condition is defined by a FlexLogic™
equation, and the number of pre-trigger cycles of data captured is programmable.
This section contains the settings (including the FlexLogic™ equation) to configure trace memory triggering.
The Trace Memory default Flexlogic is as follows:
TRACE TRIG FLEXLOGIC:
01: Any Element PKP
02 to 12: END
5.7.6 VIRTUAL OUTPUTS
Virtual outputs are FlexLogic™ equations whose output (or result) can be used as inputs to other equations.
The 745 has 5 virtual outputs. One application of these outputs may be to contain a block of logic that is
repeated for more than one output.
This section contains the FlexLogic™ equations to configure virtual outputs 1 to 5.
VIRTUAL OUTPUT 1 (2-5)
y
TRACE MEMORY
y
[ENTER] for more
This message indicates the start of the
TRACE MEMORY
section. To continue
these setpoints press
or press
for the next section.
NO. OF PRE-TRIGGER
CYCLES: 12 cycles
Range: 1 to 15 (steps of 1)
Enter the number of cycles of data, of the 16 cycles of waveform data to be
captured, that are to be pre-trigger information.
TRACE TRIG FLEXLOGIC
01: Any Element PKP
Range: any FlexLogic™ input or gate
The following 10 messages are the parameters of the FlexLogic™ equation
for trace memory triggering as described in the introduction to FlexLogic™.
y
VIRTUAL OUTPUTS
y
[ENTER] for more
This message indicates the start of the
VIRTUAL OUTPUTS
section. To
continue these setpoints press
or press
for the next section.
y
VIRTUAL OUTPUT 1
y
[ENTER] for more
This message indicates the start of the VIRTUAL OUTPUT 1 (2-5) section.
To continue these setpoints press
or press
for the next
section.
VIRTUAL 1 FLEXLOGIC
01: END
Range: any FlexLogic™ input or gate
The following 10 messages are the parameters of the FlexLogic™ equation
for virtual output 1 (2-5) as described in the introduction to FlexLogic™.
EN T E R
M E SSA G E
E N TE R
M E SSA G E
EN TE R
M E SS A G E
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...