5-4
745 Transformer Management Relay
GE Power Management
5.2 AUTO-CONFIGURATION
5 SETPOINTS
5
745 Solution:
The transformer type is entered as the setpoint
S2 SYSTEM SETUP/TRANSFORMER/TRANSFORMER TYPE
. The 745
calculates and automatically corrects for CT mismatch to a maximum mismatch factor of 16. The following
information is entered as setpoints:
For a 3-winding transformer, the setpoints under
S2 SYSTEM SETUP/WINDING 3
must also be set.
b) PROBLEM 2: ONLOAD TAP CHANGER
•
Onload tap changer
•
Variable voltage ratio
•
CT
2
/ CT
1
=
V
1
/
V
2
•
Lower sensitivity on differential element
Solution:
•
Tap position monitoring
V
2
=
V
min
+ (
n
– 1)
V
incr
Example:
The onload tap changer changes the Winding 2 voltage, resulting in an even greater CT mismatch. A perfectly
matched Winding 2 CT ratio (based on the tap changer position) is calculated as follows:
where
n
= current tap changer position
V
2(min)
= Winding 2 minimum voltage (at
n
= 1)
V
2(tap)
= Winding 2 voltage increment per tap
Thus, with the tap changer at position 33, the Winding 2 CT ratio must be 1428.6 / 1 to be perfectly matched. In
this case, the mismatch factor is 1428.6 / 1500 = 0.952.
745 Solution:
The 745 allows monitoring of the tap changer position via the tap position input. With this input, the 745 dynam-
ically adjusts the CT ratio mismatch factor based on the actual transformer voltage ratio set by the tap changer.
Under
S2 SYSTEM SETUP / WINDING 1:
Under
S2 / SYSTEM SETUP / WINDING 2:
WINDING 1 NOM
Φ
-
Φ
VOLTAGE: 220.0 kV
WINDING 2 NOM
Φ
-
Φ
VOLTAGE: 69.0 kV
WINDING 1 RATED
LOAD: 100 MVA
WINDING 2 RATED
LOAD: 100 MVA
WINDING 1 PHASE CT
PRIMARY: 500:1 A
WINDING 2 PHASE CT
PRIMARY: 1500:1 A
CT
2
(ideal)
CT
1
V
1
V
2 min
(
)
V
2 tap
(
)
n
1
–
(
)
+
-----------------------------------------------------------
×
500
1
----------
220
61
0.5
n
1
–
(
)
+
---------------------------------------
×
=
=
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...