5.2 AUTO-CONFIGURATION
5
5.2.8 TABLE OF PHASE SHIFTS
This table provides additional information about the Phase Shift column in Table 5–1: TRANSFORMER
TYPES on page 5–10 and represents an assumed ABC phasor rotation. For transformers connected to a sys-
tem with a phasor rotation of ACB, interchange all B (b) and C (c) designations.
Table 5–2: PHASE SHIFTS
PHASE
SHIFT
INPUT
PHASORS
OUTPUT
PHASORS
PHASOR
TRA NSFO RM ATIO N
PHASE
SHIFT
INPUT
PHASORS
OUTPUT
PHASORS
PHASOR
TRA NSFO RM ATIO N
0°
a = A
b = B
c = C
180° lag
a = –A
b = –B
c = –C
30° lag
a = (A – C) /
√
3
b = (B – A) /
√
3
c = (C – B) /
√
3
210° lag
a = (C – A) /
√
3
b = (A – B) /
√
3
c = (B – C) /
√
3
60° lag
a = –C
b = –A
c = –B
240° lag
a = C
b = A
c = B
90° lag
a = (B – C) /
√
3
b = (C – A) /
√
3
c = (A – B) /
√
3
270° lag
a = (C – B) /
√
3
b = (A – C) /
√
3
c = (B – A) /
√
3
120° lag
a = B
b = C
c = A
300° lag
a = –B
b = –C
c = –A
150° lag
a = (B – A) /
√
3
b = (C – B) /
√
3
c = (A – C) /
√
3
330° lag
a = (A – B) /
√
3
b = (B – C) /
√
3
c = (C – A) /
√
3
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...