8-52
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
2068
Reserved
↓
↓
↓
↓
↓
↓
↓
206F
Reserved
WINDING 1
PHASE INST
O/C 1
2070
Winding 1 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2071
Winding 1 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2072
Winding 1 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000 = 10.00 x CT
2073
Winding 1 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2074
Winding 1 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2075
Reserved
↓
↓
↓
↓
↓
↓
↓
207F
Reserved
WINDING 2
PHASE INST
O/C 1
2080
Winding 2 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2081
Winding 2 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2082
Winding 2 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
10.00 x CT
2083
Winding 2 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2084
Winding 2 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2085
Reserved
↓
↓
↓
↓
↓
↓
↓
208F
Reserved
WINDING 3
PHASE INST
O/C 1
2090
Winding 3 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2091
Winding 3 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2092
Winding 3 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
2093
Winding 3 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2094
Winding 3 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2095
Reserved
↓
↓
↓
↓
↓
↓
↓
209F
Reserved
WINDING 1
PHASE INST
O/C 2
20A0
Winding 1 Phase Inst O/C 2 Function
---
---
---
F30
1 = Enabled
20A1
Winding 1 Phase Inst O/C 2 Target
---
---
---
F46
1 = Latched
20A2
Winding 1 Phase Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
20A3
Winding 1 Phase Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
20A4
Winding 1 Phase Inst O/C 2 Block
---
---
---
F87
0 = Disabled
20A5
Reserved
↓
↓
↓
↓
↓
↓
↓
20AF
Reserved
WINDING 2
PHASE INST
O/C 2
20B0
Winding 2 Phase Inst O/C 2 Function
---
---
---
F30
1 = Enabled
20B1
Winding 2 Phase Inst O/C 2 Target
---
---
---
F46
1 = Latched
20B2
Winding 2 Phase Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
Table 8–6: 745 MEMORY MAP (Sheet 36 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...