GE Power Management
745 Transformer Management Relay
6-9
6 ACTUAL VALUES
6.3 A2 METERING
6
6.3.6 VOLTAGE
6.3.7 DEMAND
The 745 measures current demand on each phase of each monitored winding. These parameters can be mon-
itored to reduce supplier demand penalties or for statistical metering purposes. Demand is calculated based on
the measurement type in
S2 SYSTEM SETUP/DEMAND METERING
. For each quantity, the 745 displays the demand
over the most recent demand time interval, the maximum demand since the last date that the demand data
was reset, and the time and date stamp of this maximum value.
a) DEMAND DATA CLEAR
y
VOLTAGE
y
[ENTER] for more
This message indicates the start of the Voltage actual values. To view these
actual values press
or press
for the next section.
SYSTEM LINE-TO-LINE
VOLTAGE: 0.00 kV
This message displays the system’s line-to-line voltage. For phase-to-
neutral input voltages, this display is converted to its line-to-line equivalent.
VOLTS-PER-HERTZ:
0.00 V/Hz
This message displays the calculated volts-per-hertz.
LINE-NTRL VOLTAGE:
0.00 kV at 0°Lag
This message displays the line-to-neutral phase voltage magnitude and
angle.
y
DEMAND
y
[ENTER] for more
This message indicates the start of the Demand actual values. To view these
actual values press
or press
for the next section.
y
DEMAND DATA CLEAR
y
[ENTER] for more
This message indicates the start of the Demand Data Clear actual values. To
view these actual values press
or press
for the next section.
CLEAR MAX DEMAND
DATA? No
Enter
Yes
to clear all maximum demand data.
DATE OF LAST CLEAR:
Jan 01 1996
This message displays the last date that the demand data was cleared. If the
date has never been programmed, this message will display
Jan 01 1996
.
TIME OF LAST CLEAR:
00:00:00.000
This message displays the last time that the demand data was cleared.
E N T E R
M E SSA G E
E N T E R
M E SSA G E
E N TE R
M E SS A G E
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...