GE Power Management
745 Transformer Management Relay
5-59
5 SETPOINTS
5.6 S4 ELEMENTS
5
5.6.9 RESTRICTED GROUND (DIFFERENTIAL GROUND)
a) WINDING 1 (2/3) RESTRICTED GROUND FAULT
This section contains the settings to configure the restricted ground fault elements.
Figure 5–9: RESTRICTED EARTH GROUND FAULT PROTECTION
Restricted Ground Fault protection is often applied to transformers having impedance grounded wye windings.
It is intended to provide sensitive ground fault detection for low magnitude fault currents which would not be
detected by the percent differential element.
Figure 5–10: RESISTANCE GROUNDED WYE WINDING
y
RESTRICTED GROUND
y
[ENTER] for more
This message indicates the start of the
RESTRICTED GROUND
section. To
continue with these setpoints press
, or press
to go to the
next section.
E N T E R
M E SSA G E
87T
87T
87TG
87TG
Rg
Rg
Wye Winding
FAULT
I
F
Delta Winding
I
P
Impedance grounded
wye winding
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...