8-74
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
8.3.2 MEMORY MAP DATA FORMATS
Table 8–7: 745 DATA FORMATS (Sheet 1 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
F1
16 bits
UNSIGNED VALUE
Example: 1234 stored as 1234
F2
16 bits
UNSIGNED VALUE
1 DECIMAL PLACE
Example: 123.4 stored as 1234
F3
16 bits
UNSIGNED VALUE
2 DECIMAL PLACES
Example: 12.34 stored as 1234
F4
16 bits
2's COMPLEMENT SIGNED VALUE
Example: –1234 stored as –1234
F5
16 bits
2's COMPLEMENT SIGNED VALUE,
1 DECIMAL PLACE
Example: –123.4 stored as –1234
F6
16 bits
2's COMPLEMENT SIGNED VALUE,
2 DECIMAL PLACES
Example: –12.34 stored as –1234
F7
32 bits
UNSIGNED LONG VALUE
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: 123456 stored as 123456
F8
32 bits
UNSIGNED LONG VALUE,
1 DECIMAL PLACE
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: 12345.6 stored as 123456
F9
32 bits
UNSIGNED LONG VALUE,
2 DECIMAL PLACES
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: 1234.56 stored as 123456
F10
32 bits
2's COMPLEMENT SIGNED LONG
VALUE
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: -123456 stored as -123456
F11
32 bits
2's COMPLEMENT SIGNED LONG
VALUE, 1 DECIMAL PLACE
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: –12345.6 stored as –123456
F12
32 bits
2's COMPLEMENT SIGNED LONG
VALUE, 2 DECIMAL PLACES
1st 16 bits
high order word of long value
2nd 16 bits
low order word of long value
Example: –1234.56 stored as –123456
F13
16 bits
HARDWARE REVISION
0000 0000 0000 0001 1 = A
0000 0000 0000 0010 2 = B
↓
↓
0000 0000 0001 1010 26 = Z
F14
16 bits
SOFTWARE REVISION
xxxx 1111 xxxx xxxx
Major Revision Number
0 to 9 in steps of 1
xxxx xxxx 1111 xxxx
Minor Revision Number
0 to 9 in steps of 1
xxxx xxxx xxxx 1111
Ultra Minor Revision Number
0 to 9 in steps of 1
Example: Revision 2.83 stored as 0283 hex
F15
16 bits
INSTALLED OPTIONS
xxxx xxxx xxxx xxx1
Windings Per Phase (0 = Two
Windings, 1 = Three Windings)
xxxx xxxx xxxx xx1x
Rating of Winding 1 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxxx x1xx
Rating of Winding 2 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxxx 1xxx
Rating of Winding 3 Phase Current
Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xxx1 xxxx
Rating of Winding 1/2 Ground
Current Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx xx1x xxxx
Rating of Winding 2/3 Ground
Current Inputs (0 = 1 A, 1 = 5 A)
xxxx xxxx x1xx xxxx
Control Power (0=LO [20-60 Vdc],
1 = HI [90-300 Vdc/70-265 Vac])
xxxx xxxx 1xxx xxxx
Analog Input/Outputs (0 = Not
Installed, 1 = Installed)
xxxx xxx1 xxxx xxxx
Loss-Of-Life (0 = Not Installed,
1 = Installed)
xxxx xx1x xxxx xxxx
Restricted Ground Fault (0 = Not
Installed, 1 = Installed)
F16
16 bits
DEMAND INTERVAL/RESPONSE
0000 0000 0000 0000 0 = 5 min
0000 0000 0000 0001 1 = 10 min
0000 0000 0000 0010 2 = 15 min
Table 8–7: 745 DATA FORMATS (Sheet 2 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...