GE Power Management
745 Transformer Management Relay
8-7
8 COMMUNICATIONS
8.2 MODBUS PROTOCOL
8
8.2.10 FUNCTION CODE 05H: EXECUTE OPERATION
Modbus implementation:
Force Single Coil
GE Power Management implementation:
Execute Operation
This function code allows the master to perform various operations in the 745. The 2 byte CODE VALUE of
FF00h must be sent after the OPERATION CODE for the operation to be performed.
MESSAGE FORMAT AND EXAMPLE:
Request to perform reset operation in slave device 11.
Master Query Message:
Example (hex):
SLAVE ADDRESS
11
query message for slave 11
FUNCTION CODE
05
execute operation
OPERATION CODE: high order byte
00
remote reset
OPERATION CODE: low order byte
01
CODE VALUE: high order byte
FF
perform operation
CODE VALUE: low order byte
00
CRC: low order byte
DF
CRC: high order byte
6A
Field:
Example (hex):
SLAVE ADDRESS
11
response message from slave 11
FUNCTION CODE
05
execute operation
OPERATION CODE: high order byte
00
remote reset
OPERATION CODE: low order byte
01
CODE VALUE: high order byte
FF
perform operation
CODE VALUE: low order byte
00
CRC: low order byte
DF
CRC: high order byte
6A
Table 8–2: SUMMARY OF OPERATION CODES FOR FUNCTION CODE 05H
OPERATION
CODE
DEFINITION
DESCRIPTION
0000
NO OPERATION
Does not do anything.
0001
REMOTE RESET
Performs the same function as the front panel RESET key.
0002
TRIGGER TRACE
MEMORY
Initiates a waveform capture of trace memory and increments the "Total Number
of Trace Triggers" registers.
0003
CLEAR MAXIMUM
DEMAND DATA
Performs the same function as the command in message
A2 METERING / DEMAND
/ DEMAND DATA CLEAR / CLEAR MAXIMUM DEMAND DATA
.
0004
CLEAR EVENT
RECORDER DATA
Performs the same function as the command in message
A3 EVENT RECORDER /
EVENT DATA CLEAR / CLEAR EVENT RECORDER DATA
.
0005
CLEAR LOSS-OF-
LIFE DATA
Performs the same function as the command in message
S1 745 SETUP /
INSTALLATION / CLEAR LOSS-OF-LIFE DATA
.
0006
CLEAR TRACE
MEMORY
Clears all trace memory buffers and sets the "Total Number of Trace Triggers"
register to zero.
0007
CLEAR ENERGY
DATA
Performs the same function as the command in message
A2 METERING / ENERGY /
ENERGY DATA CLEAR / CLEAR ENERGY
.
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...