GE Power Management
745 Transformer Management Relay
3-5
3 INSTALLATION
3.2 TYPICAL WIRING
3
3.2.3 REAR TERMINAL ASSIGNMENTS
n
indicates high side of CT and VT terminals
ANALOG INTERFACE
OUTPUTS & GROUND CT N2
A1
ANALOG INPUT +
E1
OUTPUT 1 - SOLID STATE TRIP (+)
A2
ANALOG INPUT –
E2
OUTPUT 2 - TRIP RELAY (N/O)
A3
TAP POSITION (+)
E3
OUTPUT 3 - TRIP RELAY (N/O)
A4
TAP POSITION (–)
E4
OUTPUT 4 - TRIP RELAY (N/O)
A5
ANALOG OUTPUT (Common)
E5
OUTPUT 5 - TRIP RELAY (N/O)
A6
ANALOG OUTPUT 1 (+)
E6
OUTPUT 6 - AUXILIARY RELAY (N/O)
A7
ANALOG OUTPUT 2 (+)
E7
OUTPUT 6 - AUXILIARY RELAY (N/C)
A8
ANALOG OUTPUT 3 (+)
E8
OUTPUT 7 - AUXILIARY RELAY (N/O)
A9
ANALOG OUTPUT 4 (+)
E9
OUTPUT 8 - AUXILIARY RELAY (N/O)
A10
ANALOG OUTPUT 5 (+)
E10
OUTPUT 8 - AUXILIARY RELAY (N/C)
A11
ANALOG OUTPUT 6 (+)
E11
OUTPUT 9 - SERVICE RELAY (Common)
A12
ANALOG OUTPUT 7 (+)
E12
GROUND - WINDING 2/3 CT
COMMUNICATIONS & RTD INPUTS
OUTPUTS & GROUND CT N2
B1
COMPUTER RS485 (+) / RS422 (Rx +)
F1
OUTPUT 1 - SOLID STATE TRIP (–)
B2
COMPUTER RS485 (–) / RS422 (Rx –)
F2
OUTPUT 2 - TRIP RELAY (Common)
B3
COMPUTER RS485 (Com) / RS422 (Com)
F3
OUTPUT 3 - TRIP RELAY (Common)
B4
RS422 (Tx +)
F4
OUTPUT 4 - TRIP RELAY (Common)
B5
RS422 (Tx –)
F5
OUTPUT 5 - TRIP RELAY (Common)
B6
EXTERNAL RS485 (+)
F6
OUTPUT 6 - AUXILIARY RELAY (
Common
)
B7
EXTERNAL RS485 (–)
F7
OUTPUT 7 - AUXILIARY RELAY (N/O)
B8
IRIG-B +
F8
OUTPUT 7 - AUXILIARY RELAY (N/C)
B9
IRIG-B –
F9
OUTPUT 8 - AUXILIARY RELAY (
Common
)
B10
RTD 1 HOT
F10
OUTPUT 9 - SERVICE RELAY (N/O)
B11
RTD 1 COMPENSATION
F11
OUTPUT 9 - SERVICE RELAY (N/C)
B12
RTD 1 RETURN
F12
GROUND - WINDING 2/3 CT
n
LOGIC INPUTS 9-16 & VT INPUT
CT INPUTS & 745 GROUNDING
C1
LOGIC INPUT 9 (+)
G1
PHASE A - WINDING 1 CT
C2
LOGIC INPUT 10 (+)
G2
PHASE B - WINDING 1 CT
C3
LOGIC INPUT 11 (+)
G3
PHASE C - WINDING 1 CT
C4
LOGIC INPUT 12 (+)
G4
PHASE A - WINDING 2 CT
C5
LOGIC INPUT 13 (+)
G5
PHASE B - WINDING 2 CT
C6
LOGIC INPUT 14 (+)
G6
PHASE C - WINDING 2 CT
C7
LOGIC INPUT 15 (+)
G7
PHASE A - WINDING 3 CT
C8
LOGIC INPUT 16 (+)
G8
PHASE B - WINDING 3 CT
C9
RESERVED
G9
PHASE C - WINDING 3 CT
C10
RESERVED
G10
GROUND - WINDING 1/2 CT
C11
VT INPUT
n
G11
745 FILTER GROUND
C12
VT INPUT
G12
745 SAFETY GROUND
LOGIC INPUTS 1-8 & DEDICATED INPUTS
CT and VT INPUTS / POWER
D1
LOGIC INPUT 1 (+)
H1
PHASE A - WINDING 1 CT
n
D2
LOGIC INPUT 2 (+)
H2
PHASE B - WINDING 1 CT
n
D3
LOGIC INPUT 3 (+)
H3
PHASE C - WINDING 1 CT
n
D4
LOGIC INPUT 4 (+)
H4
PHASE A - WINDING 2 CT
n
D5
LOGIC INPUT 5 (+)
H5
PHASE B - WINDING 2 CT
n
D6
LOGIC INPUT 6 (+)
H6
PHASE C - WINDING 2 CT
n
D7
LOGIC INPUT 7 (+)
H7
PHASE A - WINDING 3 CT
n
D8
LOGIC INPUT 8 (+)
H8
PHASE B - WINDING 3 CT
n
D9
SETPOINT ACCESS (+)
H9
PHASE C - WINDING 3 CT
n
D10
SETPOINT ACCESS (–)
H10
GROUND - WINDING 1/2 CT
n
D11
LOGIC POWER OUT (+)
H11
CONTROL POWER (–)
D12
LOGIC POWER OUT (–)
H12
CONTROL POWER (+)
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...