8
CURRENT
DEMAND
continued
0456
Winding 1 Phase C Current Demand
---
---
A
F78
---
0457
Winding 1 Max Current Demand
---
---
A
F78
0 A
0458
Winding 1 Max Current Demand Phase
---
---
---
F18
0 = phase A
0459
Wdg 1 Max Current Demand Date (2 registers)
---
---
---
F23
Jan 01 1996
045B
Wdg 1 Max Current Demand Time (2 registers)
---
---
---
F22
00:00:00.000
045D
Winding 2 Phase A Current Demand
---
---
A
F79
---
045E
Winding 2 Phase B Current Demand
---
---
A
F79
---
045F
Winding 2 Phase C Current Demand
---
---
A
F79
---
0460
Winding 2 Max Current Demand
---
---
A
F79
0 A
0461
Winding 2 Max Current Demand Phase
---
---
---
F18
0 = phase A
0462
Wdg 2 Max Current Demand Date (2 registers)
---
---
---
F23
Jan 01 1996
0464
Wdg 2 Max Current Demand Time (2 registers)
---
---
---
F22
00:00:00.000
0466
Winding 3 Phase A Current Demand
---
---
A
F80
---
0467
Winding 3 Phase B Current Demand
---
---
A
F80
---
0468
Winding 3 Phase C Current Demand
---
---
A
F80
---
0469
Winding 3 Max Current Demand
---
---
A
F80
0 A
046A
Winding 3 Max Current Demand Phase
---
---
---
F18
0 = phase A
046B
Wdg 3 Max Current Demand Date (2 registers)
---
---
---
F23
Jan 01 1996
046D
Wdg 3 Max Current Demand Time (2 registers)
---
---
---
F22
00:00:00.000
046F
Reserved
↓
↓
↓
↓
↓
↓
↓
0477
Reserved
AMBIENT
TEMP
0478
Ambient Temperature
–51 to 251
1
°C
F4
---
0479
Reserved
↓
↓
↓
↓
↓
↓
↓
047F
Reserved
LOSS-OF-LIFE
0480
Hottest-spot Winding Temperature
–50 to 300
1
°C
F4
---
0481
Total Accumulated Loss-of-Life (2 registers)
0 to 200000
1
hours
F7
0 hours
0483
Aging Factor
0.0 to 2000.0
0.1
-
F2
-
↓
↓
↓
↓
↓
↓
↓
0487
Reserved
ANALOG
INPUT
0488
Analog Input
0 to 65000
1
<Units>
F1
---
0489
Reserved
↓
↓
↓
↓
↓
↓
↓
048F
Reserved
POWER
0490
W1 Real Power
–32000 to 32000
---
MW
F93
---
0491
W1 Reactive Power
–32000 to 32000
---
Mvar
F93
---
0492
W1 Apparent Power
0 to 32000
---
MVA
F93
---
Table 8–6: 745 MEMORY MAP (Sheet 15 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...