GE Power Management
745 Transformer Management Relay
5-27
5 SETPOINTS
5.3 S1 745 SETUP
5
5.3.5 DNP COMMUNICATIONS
When "Disabled" is selected, a cold restart request will cause loss of protection until the 745
reset completes.
y
DNP
y
[ENTER] for more
This message indicates the start of the
DNP COMMUNICATION
page. To
continue with these setpoints press
, or press
to go back to
the PORT SETUP section.
DNP PORT:
None
Range: None / Com1 / Com2 / Front
Select the communication port that you will use for DNP.
DNP POINT MAPPING:
Enabled
Range: Enabled / Disabled
When enabled, the 120 User Map Values are included in the DNP Object 30
point list. For more information, refer to Section 8.4: DNP
COMMUNICATIONS.
TRANSMISSION DELAY:
0 ms
Range: 0 to 65000 (Steps of 1)
Select the minimum time from when a DNP request is received and a
response issued. A value of zero causes the response to be issued as
quickly as possible.
DATA LINK CONFIRM
MODE: Never
Range: Never / Always / Sometimes
Select the data link confirmation mode desired for responses sent by the
745. When
Sometimes
is selected, data link confirmation is only requested
when the response contains more than one frame.
DATA LINK CONFIRM
TIMOUT: 1000 ms
Range: 1 to 65000 (Steps of 1)
Select a desired timeout. If no confirmation response is received within this
time, the 745 will resend the frame if retries are still available.
DATA LINK CONFIRM
RETRIES: 3
Range: 0 to 100 (Steps of 1)
Select the maximum number of retries that will be issued for a given data link
frame.
SELECT/OPERATE ARM
TIMEOUT: 10000 ms
Range: 1 to 65000 (Steps of 1)
Select the duration of the select / operate arm timer.
WRITE TIME INTERVAL:
0 min.
Range: 0 to 65000 (Steps of 1)
Select the time that must elapse before the 745 will set the "need time"
internal indication (IIN). After the time is written by a DNP master, the IIN will
be set again after this time elapses. A value of zero disables this feature.
COLD RESTART
INHIBIT: Disabled
Range: Enabled / Disabled
When disabled, a cold restart request from a DNP master will cause the 745
to be reset. Enabling this setpoint will cause the cold restart request to
initialize only the DNP sub-module.
EN T E R
M E SS A G E
WARNING
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...