8-58
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
WINDING 3
RESTD GND
FAULT
2210
Winding 3 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
2211
Winding 3 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
2212
Winding 3 Restricted Ground Fault Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2213
Winding 3 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
2214
Winding 3 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2215
Winding 3 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
2216
Reserved
↓
↓
↓
↓
↓
↓
↓
221F
Reserved
WINDING 1
RESTD GND
TREND
2220
Winding 1 Restricted Ground Trend Function
---
---
---
F30
0 = Disabled
2221
Winding 1 Restricted Ground Trend Target
---
---
---
F46
1 = Latched
2222
Winding 1 Restricted Ground Trend Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2223
Winding 1 Restricted Ground Trend Slope
0 to 100
1
%
F1
90%
2224
Winding 1 Restricted Ground Trend Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2225
Winding 1 Restricted Ground Trend Block
---
---
---
F87
0 = Disabled
2226
Reserved
↓
↓
↓
↓
↓
↓
↓
222F
Reserved
WINDING 2
RESTD GND
TREND
2230
Winding 2 Restricted Ground Trend Function
---
---
---
F30
0 = Disabled
2231
Winding 2 Restricted Ground Trend Target
---
---
---
F46
1 = Latched
2232
Winding 2 Restricted Ground Trend Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2233
Winding 2 Restricted Ground Trend Slope
0 to 100
1
%
F1
90%
2234
Winding 2 Restricted Ground Trend Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2235
Winding 2 Restricted Ground Trend Block
---
---
---
F87
0 = Disabled
2236
Reserved
↓
↓
↓
↓
↓
↓
↓
223F
Reserved
WINDING 3
RESTD GND
TREND
2240
Winding 3 Restricted Ground Trend Function
---
---
---
F30
0 = Disabled
2241
Winding 3 Restricted Ground Trend Target
---
---
---
F46
1 = Latched
2242
Winding 3 Restricted Ground Trend Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2243
Winding 3 Restricted Ground Trend Slope
0 to 100
1
%
F1
90%
2244
Winding 3 Restricted Ground Trend Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2245
Winding 3 Restricted Ground Trend Block
---
---
---
F87
0 = Disabled
2246
Reserved
↓
↓
↓
↓
↓
↓
↓
224F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 42 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...