5-64
745 Transformer Management Relay
GE Power Management
5.6 S4 ELEMENTS
5 SETPOINTS
5
b) WINDING 1 (2/3) NEG. SEQ. INSTANTANEOUS OVERCURRENT
y
W1 NEG SEQ INST OC
y
[ENTER] for more
This message indicates the start of the section describing the characteristics
of the
NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT
protection for
Winding 1 (2/3). To continue with these setpoints press
, or press
to go to the next section.
W1 NEG SEQ INST OC
FUNCTION: Disabled
Range: Disabled / Enabled
W1 NEG SEQ INST OC
TARGET: Latched
Range: Self-reset / Latched / None
Select
None
to inhibit the display of the target message when the element
operates. Thus an element whose “target type” is
None
never disables the
LED self-test feature because can not generate a displayable target
message.
W1 NEG SEQ INST OC
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 (steps of 0.01)
Enter the level of negative sequence current (in units of relay nominal
current) above which the W1 (2/3) negative sequence instantaneous
overcurrent element will pickup and start the delay timer.
W1 NEG SEQ INST OC
DELAY: 0 ms
Range: 0 to 60000 (steps of 1)
Enter the time that the negative sequence current must remain above the
pickup level before the element operates.
W1 NEG SEQ INST OC
BLOCK: Disabled
Range: Disabled / Logc Inpt 1 (2-16) /Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
E N TE R
M E SSA G E
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...