GE Power Management
745 Transformer Management Relay
1-7
1 PRODUCT OVERVIEW
1.2 TECHNICAL SPECIFICATIONS
1
PHASE / NEUTRAL / GROUND / NEGATIVE SEQUENCE TIME OVERCURRENT
Pickup Level:
0.05 to 20.00 in steps of 0.01 x CT
Dropout Level:
97 to 98% of Pickup
Curve Shape:
ANSI Extremely/Very/Moderately/Normally Inverse;
Definite Time (0.1 s base curve);
IEC Curve A/B/C and Short;
FlexCurve™ A/B/C (programmable curves);
IAC Extreme/Very/Inverse/Short
Curve Multiplier Time Dial:
0.5 to 30 for ANSI, IAC & FlexCurves™ in steps of 0.1 s;
0.05 to 100.00 for IEC curves in steps of 0.01
Reset Type:
Instantaneous or Linear
Level Accuracy:
Per current input
Timing Accuracy:
at
≥
1.03
×
pickup: ± 3% of trip time or ± 20 ms (whichever is greater)
PHASE / NEUTRAL / GROUND / NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT
Pickup Level:
0.05 to 20.00 in steps of 0.01
×
CT
Dropout Level:
97 to 98% of Pickup
Time Delay:
0 to 60000 in steps of 1 ms
Level Accuracy:
Per current input
Operate Time:
Solid State Output: at 1.2
×
pickup: 22 to 30 ms
at 2.0
×
pickup: 18 to 26 ms
at 4.0
×
pickup: 11 to 19 ms
Relay Outputs 2-5: at 1.2
×
pickup: 28 to 36 ms
at 2.0
×
pickup: 24 to 32 ms
at 4.0
×
pickup: 17 to 25 ms
UNDERFREQUENCY (2 ELEMENTS)
Operating Current Pickup:
0.05 to 1.00 in steps of 0.01
×
CT
Operating Voltage Pickup
0.10 to 0.99 in steps of 0.01
×
VT
Pickup Level:
45.00 to 59.99 in steps of 0.01 Hz
Dropout Level:
0.03 Hz
Time Delay:
0.00 to 600.00 s in steps of 0.01 s
Signal Source:
Winding 1 phase A current / voltage
Level Accuracy:
±0.02 Hz
Operate Time:
Solid State Output:
at 3% beyond pickup: 120 to 150 ms
Relay Outputs 2 to 5: at 3% beyond pickup: 125 to 155 ms (delay set at 0.0 sec.)
FREQUENCY RATE OF CHANGE (4 ELEMENTS)
Operating Current Pickup:
0.05 to 1.00 in steps of 0.01
×
CT
Operating Voltage Pickup
0.10 to 0.99 in steps of 0.01
×
VT
Pickup Level:
45.00 to 59.99 in steps of 0.01 Hz
Dropout Level:
0.03 Hz
Rate 1/2/3/4:
0.1 to 5.0 in steps of 0.1 Hz/sec.
Dropout Level:
0.07 Hz/sec.
Signal Source:
Winding 1 phase A current / voltage
Level Accuracy:
±0.02 Hz
Operate Time:
The operate time of the frequency trend element is variable and is dependent on the decay
rate setting and the supervision frequency level.
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...