GE Power Management
745 Transformer Management Relay
6-19
6 ACTUAL VALUES
6.6 TARGET MESSAGES
6
6.6 TARGET MESSAGES
6.6.1 DESCRIPTION
Target messages are displayed when any protection, monitoring or self-test target is activated. The messages
contain information about the type of the active target(s), and are displayed in a queue that is independent of
both the setpoint and actual value message structures.
When any target is active, the MESSAGE indicator will light, and the first message in the queue is displayed
automatically. The target message queue may be scrolled through by pressing
.
If no key is pressed, the next target message in the queue will be displayed after a delay of four seconds. This
process repeats, continuously cycling through the queue of target messages.
As long as there is at least one message in the queue, the MESSAGE indicator will remain lit. Pressing any
key other than
will return the display to the setpoint or actual value message that was previously dis-
played. The
key may be pressed any time the MESSAGE indicator is lit, to redisplay the target message
queue.
If
is pressed when no target messages are in the queue, all front-panel LEDs will light and the flash
message
will appear. A typical active target message looks like this,
and consists of three components which are arranged thus:
<STATUS>
will be one of
PICKUP
,
OPERATE
or
LATCHED
.
•
PICKUP: Indicates that the fault condition that is required to activate the protection element has been
detected by the 745 but has not persisted for a sufficiently long time to cause the relay to activate its pro-
tection function.
•
OPERATE: Indicates that the protection element has been activated.
•
LATCHED: Indicates that the protection element is (or was) activated. This display will remain even if the
conditions that caused the element to activate are removed.
•
<PHASE> are the phase(s) that are associated with the element (where applicable).
Messages for
LATCHED
targets remain in the queue until the relay is reset. Messages for
PICKUP
and
OPERATE
targets remain in the queue as long as the condition causing the target to be active is present.
In addition, messages for
LATCHED
targets will automatically be deleted if an entire week passes without any
changes to the state of the target messages but the conditions that caused the
LATCHED
messages to be dis-
played originally are no longer present.
yy
NO ACTIVE TARGETS
yy
(TESTING LEDS)
y
LATCHED: a
y
Percent Differentl
y
<STATUS>: <PHASE>
y
<CAUSE>
N EX T
N EX T
N E X T
N E X T
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...