8-94
745 Transformer Management Relay
GE Power Management
8.4 DNP COMMUNICATIONS
8
8.4.2 IMPLEMENATION TABLE
The table below gives a list of all objects recognized and returned by the relay. Additional information is pro-
vided on the following pages including a list of the default variations returned for each object and lists of
defined point numbers for each object.
Table Notes:
1.
For this object, the quantity specified in the request must be exactly 1 as there is only one instance of this object
defined in the relay.
2.
All static input data known to the relay is returned in response to a request for Class 0. This includes all objects of type
1 (Binary Input), type 10 (Binary Output) and type 30 (Analog Input).
3.
The point tables for Binary Input and Analog Input objects contain a field which defines to which event class the corre-
sponding static data has been assigned.
4.
For this object, the qualifier code must specify an index of 7 only.
IMPLEMENTATION TABLE
OBJECT
REQUEST
RESPONSE
Obj
Var
Description
Func. Codes
Qual Codes (Hex)
Func. Codes
Qual Codes (Hex)
1
0
Binary Input - All Variations
1
06
1
1
Binary Input
1
00, 01, 06
129
00, 01
1
2
Binary Input With Status
1
00, 01, 06
129
00, 01
2
0
Binary Input Change - All Variations
1
06, 07, 08
2
1
Binary Input Change Without Time
1
06, 07, 08
129
17, 28
2
2
Binary Input Change With Time
1
06, 07, 08
129
17, 28
10
0
Binary Output - All Variations
1
06
10
2
Binary Output Status
1
00, 01, 06
129
00, 01
12
1
Control Relay Output Block
3, 4, 5, 6
17, 28
129
17, 28
30
0
Analog Input - All Variations
1
06
30
1
32-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
2
16-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
3
32-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
30
4
16-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
32
0
Analog Input Change - All Variations
1
06, 07, 08
32
1
32-Bit Analog Input Change Without Time
1
06, 07, 08
129
17, 28
32
2
16-Bit Analog Input Change Without Time
1
06, 07, 08
129
17, 28
32
3
32-Bit Analog Input Change With Time
1
06, 07, 08
129
17, 28
32
4
16-Bit Analog Input Change With Time
1
06, 07, 08
129
17, 28
50
1
Time and Date
1, 2
07 (Note 1)
129
07
60
1
Class 0 Data (Note 2)
1
06
129
60
2
Class 1 Data (Note 3)
1
06, 07, 08
129
60
3
Class 2 Data (Note 3)
1
06, 07, 08
129
60
4
Class 3 Data (Note 3)
1
06, 07, 08
129
80
1
Internal Indications
2
00 (Note 4)
129
No object
13
No object
14
No object
23
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...