GE Power Management
745 Transformer Management Relay
3-9
3 INSTALLATION
3.2 TYPICAL WIRING
3
3.2.8 CONTROL POWER
Control power supplied to the relay must match the installed power supply range. If the
applied voltage does not match, damage to the unit may occur.
The label found on the left side of the relay specifies its order code or model number. The installed power sup-
ply operating range will be one of the following.
LO:
25 to 60 V DC or 20 to 48 V AC
HI:
88 to 300 V DC or 70 to 265 V AC
Ensure the applied control voltage matches the requirements of the relay’s switching power supply. For exam-
ple, the HI power supply will work with any DC voltage from 88 to 300 V, or any AC voltage from 70 to 265 V.
The internal fuse may blow if the applied voltage exceeds this range.
Figure 3–10: CONTROL POWER CONNECTION
3.2.9 LOGIC INPUTS
Correct polarity must be observed for all logic input connections or equipment damage may
result.
External contacts can be connected to the 16 logic inputs. As shown, these contacts can be either dry or wet. It
is also possible to use a combination of both contact types.
A dry contact has one side connected to terminal D11. This is the +32 V DC voltage rail. The other side of the
dry contact is connected to the required logic input terminal. When a dry contact closes, a current of 2.2 mA will
flow through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side
of this contact is connected to the required logic input terminal. In addition, the negative side of the external
source must be connected to the relay DC NEGATIVE rail at terminal D12. The maximum external source volt-
age for this arrangement is 300 V DC.
WARNING
CAUTION
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...