8-98
745 Transformer Management Relay
GE Power Management
8.5 POINT LISTS
8
In the following table, the entry in the “Format” column indicates that the format of the associated data point
can be determined by looking up the entry in the
Memory Map Data Formats
table. For example, an “F1” for-
mat is described in that table as a (16-bit) unsigned value without any decimal places. Therefore, the value
read should be interpreted in this manner.
POINT LIST FOR:
ANALOG INPUT (OBJECT 30)
ANALOG INPUT CHANGE (OBJECT 32)
(Note 5) Index when
Point Mapping Is:
Format
Description
Event Class
Assigned To
Notes
Disabled
Enabled
n/a
0
-
User Map Value 1
n/a
1
-
User Map Value 2
.
.
-
.
.
.
-
.
.
.
-
.
n/a
118
-
User Map Value 119
n/a
119
-
User Map Value 120
0
120
F1
Winding 1 Phase CT Primary
Class 1
Notes 2,6
1
121
F1
Winding 2 Phase CT Primary
Class 1
Notes 2,7
2
122
F1
Winding 3 Phase CT Primary
Class 1
Notes 2,5,8
3
123
F1
Winding 1 Ground CT Primary
Class 1
Notes 2,9
4
124
F1
Winding 2 Ground CT Primary
Class 1
Notes 2,10
5
125
F1
Winding 3 Ground CT Primary
Class 1
Notes 2,5,11
6
126
F78
Winding 1 Phase A Current Magnitude
Class 1
Note 6
7
127
F78
Winding 1 Phase B Current Magnitude
Class 1
Note 6
8
128
F78
Winding 1 Phase C Current Magnitude
Class 1
Note 6
9
129
F78
Winding 1 Neutral Current Magnitude
Class 1
Note 6
10
130
F81
Winding 1 Ground Current Magnitude
Class 1
Notes 5,9
11
131
F1
Winding 1 Loading
Class 1
12
132
F78
Winding 1 Average Phase Current Magnitude
Class 1
Note 6
13
133
F79
Winding 2 Phase A Current Magnitude
Class 1
Note 7
14
134
F79
Winding 2 Phase B Current Magnitude
Class 1
Note 7
15
135
F79
Winding 2 Phase C Current Magnitude
Class 1
Note 7
16
136
F79
Winding 2 Neutral Current Magnitude
Class 1
Note 7
17
137
F82
Winding 2 Ground Current Magnitude
Class 1
Note 5,10
18
138
F1
Winding 2 Loading
Class 1
19
139
F79
Winding 2 Average Phase Current Magnitude
Class 1
Note 7
20
140
F80
Winding 3 Phase A Current Magnitude
Class 1
Notes 5,8
21
141
F80
Winding 3 Phase B Current Magnitude
Class 1
Notes 5,8
22
142
F80
Winding 3 Phase C Current Magnitude
Class 1
Notes 5,8
23
143
F80
Winding 3 Neutral Current Magnitude
Class 1
Notes 5,8
24
144
F83
Winding 3 Ground Current Magnitude
Class 1
Notes 5,11
25
145
F1
Winding 3 Loading
Class 1
Note 5
26
146
F80
Winding 3 Average Phase Current Magnitude
Class 1
Notes 5,8
27
147
F78
Winding 1 Positive Sequence Current Magnitude
Class 1
Note 6
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...