5-26
745 Transformer Management Relay
GE Power Management
5.3 S1 745 SETUP
5 SETPOINTS
5
5.3.4 COMMUNICATIONS
Up to 32 relays can be daisy-chained and connected to a computer or a programmable controller, using either
the two wire RS485 or the four wire RS422 serial communication port at the rear of the 745. Before using com-
munications, each relay must be programmed with a unique address and a common baud rate.
y
COMMUNICATIONS
y
[ENTER] for more
This message indicates the start of the
COMMUNICATIONS
section. To
continue with these setpoints press
, or press
to go to the
next section.
SLAVE ADDRESS:
254
Range: 1 to 254 (steps of 1)
Enter a unique address, from 1 to 254, for this particular relay on both COM1
and COM2 serial communication links. This setpoint cannot be changed via
the communication ports. Although addresses need not be sequential, no
two relays can have the same address. Generally each relay added to the
link will use the next higher address, starting from address 1. No address is
required to use the front panel program port since only one relay can be
connected at one time.
COM1 BAUD RATE:
19200 Baud
Range: 300 / 1200 / 2400 / 4800 / 9600 / 19200
Select the baud rate for COM1, the RS485/RS422 communication port. This
setpoint cannot be changed via the communication ports. All relays on the
communication link, and the computer connecting them, must run at the
same baud rate. The fastest response is obtained at 19200 baud.
COM1 PARITY:
None
Range: None / Even / Odd
The data frame is fixed at 1 start, 8 data, and 1 stop bit. If required, a parity
bit is programmable. This setpoint cannot be changed via the
communication ports. The parity of the transmitted signal must match the
parity displayed in this setpoint.
COM1 HARDWARE:
RS485
Range: RS485 / RS422
If the two-wire RS485 hardware configuration is required for the COM1 serial
communication port, select
RS485
. This setpoint cannot be changed via the
communication ports. If the four wire RS422 hardware configuration is
required, select
RS422
.
COM2 BAUD RATE:
19200 Baud
Range: 300 / 1200 / 2400 / 4800 / 9600 / 19200
Select the baud rate for the COM2 port. This setpoint cannot be changed via
the communication ports.
COM2 PARITY:
None
Range: None / Even / Odd
Select the parity type for the COM2 port. This setpoint cannot be changed
via the communication ports.
FRONT BAUD RATE:
19200 Baud
Range: 300 / 1200 / 2400 / 4800 / 9600 / 19200
Select the baud rate for the front panel port. This setpoint cannot be
changed via the communication ports.
FRONT PARITY:
None
Range: None / Even / Odd
Select the parity type for the front panel port. This setpoint cannot be
changed via the communication ports.
E N T E R
M E SS A G E
Содержание 745 TRANSFORMER MANAGEMENT RELAY
Страница 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Страница 150: ...5 100 745 Transformer Management Relay GE Power Management 5 10 INVERSE VOLTS PER HERTZ CURVES 5 SETPOINTS 5 ...
Страница 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Страница 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Страница 392: ...11 24 745 Transformer Management Relay GE Power Management 11 1 COMMISSIONING SUMMARY 11 SETPOINT TABLES 11 ...
Страница 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 398: ...B 2 745 Transformer Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 406: ...vi 745 Transformer Management Relay GE Power Management ...
Страница 407: ...GE Power Management 745 Transformer Management Relay NOTES ...