OF-500 OptiFiber Certifying OTDR
Technical Reference Handbook
6-40
Bi-Directional Testing
You can test cabling in both directions and save the bi-
directional test results in all test modes.
Bi-Directional Testing in Smart Remote or Loopback
Mode
1
On the main tester’s
Job
tab in Setup, enter names
for
END 1
and
END 2
to identify the ends of the
cabling. Name
END 1
as the end where the main
tester will be located.
2
Set
THIS END
to
END 1
.
3
On the main tester's
Loss/Length
tab, set
BI-DIRECTIONAL
to
Enabled
.
4
Run a loss/length test on the cabling. Halfway
through the test, the tester prompts you to swap the
fibers at each end of the cabling. Swap the
connections at the patch panel, not at the tester's
ports.
5
Press
s
to save the test.
Bi-Directional Testing in Far End Source Mode
1
On the
Job
tab in Setup, enter names for
END 1
and
END 2
to identify the ends of the cabling. Name
END
1
as the end you will test first.
2
Set
THIS END
to
END 1
.
3
Test all the cabling and save the results from
END 1
.
4
On the
Job
tab, change
THIS END
to
END 2
; then test
all the cabling from the other end. When you save
each result, use the same fiber ID you used for the
results from the first end. The used IDs will be in the
IDs IN CURRENT FOLDER
list.
Diagnosing Loss/Length Test Failures
Table 6-10 describes some typical causes of loss/length test
failures.
See also the table in Appendix C, which shows results
from a survey on common causes of fiber link failures.
Содержание OF-500 OptiFiber
Страница 12: ...OF 500 OptiFiber Technical Reference Handbook x ...
Страница 18: ...OF 500 OptiFiber Technical Reference Handbook xvi ...
Страница 27: ...Getting Acquainted Powering the Tester 1 1 9 ajt20f eps Figure 1 1 Battery Pack Features ...
Страница 29: ...Getting Acquainted Verifying Operation 1 1 11 ajt56f eps Figure 1 2 Removing the Module ...
Страница 46: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 1 28 ...
Страница 95: ...Using the OTDR Running the OTDR Test 3 3 21 ajt33f eps Figure 3 12 Connecting the OTDR to Spooled Cable ...
Страница 133: ...Using the ChannelMap Function Running the Test 4 4 3 ajt55f eps Figure 4 2 ChannelMap Test Connections ...
Страница 136: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 4 6 ...
Страница 148: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 4 ajt61f eps Figure 6 2 Changing the Connector Adapter ...
Страница 192: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 48 ...
Страница 196: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 7 4 ajt03f eps Figure 7 2 Using the Visual Fault Locator ...
Страница 254: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 11 36 ...
Страница 256: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 261: ...Loss Test Methods Method A A 2 B B 3 ajt58f eps Figure B 1 Method A A 2 Reference and Test Connections singlemode shown ...
Страница 263: ...B 5 ajt59f eps Figure B 2 Method B A 1 Reference and Test Connections singlemode shown Loss Test Methods Method B A 1 B ...
Страница 265: ...Loss Test Methods Method C A 3 B B 7 ajt60f eps Figure B 3 Method C A 3 Reference and Test Connections singlemode shown ...
Страница 272: ...B 14 OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 274: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook C 2 ...
Страница 282: ...OF 500 OptiFiber Technical Reference Handbook 8 ...