Using the Loss/Length Option
Using Mandrels for Testing Multimode Fiber
6
6-15
Using Mandrels for Testing
Multimode Fiber
You should use mandrels when testing multimode fiber.
Mandrels can improve measurement repeatability and
consistency. They also allow the use of LED light sources
to certify 50 µm and 62.5 µm fiber links for current and
planned high bit-rate applications, such as Gigabit
Ethernet and 10 Gigabit Ethernet.
The gray mandrels included with some OptiFiber models
are compliant with TIA/EIA-568-B for 62.5
µ
m fiber with a
3 mm jacket. Mandrels for 50
µ
m fiber are available from
Fluke Networks. Refer to the appropriate standard for
mandrel requirements if you follow other standards.
Table 6-3 shows a partial list of mandrel requirements for
TIA and ISO standards.
Figure 6-4 shows how to wrap the fiber around a
mandrel. Place mandrels on the tester’s output fibers, as
shown in Figures 6-6 through 6-13.
In the reference and test connection diagrams shown on
the tester, mandrels are indicated by a loop in the fiber.
Table 6-3. TIA/EIA-568-B.1 and ISO/IEC TR 14763-3 Mandrel Requirements
Fiber
core size
Standard
Wraps Around
Mandrel
Mandrel Diameter for
250 µm Buffered Fiber
Mandrel Diameter for 3 mm
(0.12 in) Jacketed Cable
50 µm
TIA/EIA-568-B.1 7.1
5
25 mm (1.0 in)
22 mm (0.9 in)
ISO/IEC TR 14763-3 6.22
5
15 mm (0.6 in)
15 mm (0.6 in)
62.5 µm
TIA/EIA-568-B.1 7.1
5
20 mm (0.8 in)
17 mm (0.7 in)
ISO/IEC TR 14763-3 6.22
5
20 mm (0.8 in)
20 mm (0.8 in)
Содержание OF-500 OptiFiber
Страница 12: ...OF 500 OptiFiber Technical Reference Handbook x ...
Страница 18: ...OF 500 OptiFiber Technical Reference Handbook xvi ...
Страница 27: ...Getting Acquainted Powering the Tester 1 1 9 ajt20f eps Figure 1 1 Battery Pack Features ...
Страница 29: ...Getting Acquainted Verifying Operation 1 1 11 ajt56f eps Figure 1 2 Removing the Module ...
Страница 46: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 1 28 ...
Страница 95: ...Using the OTDR Running the OTDR Test 3 3 21 ajt33f eps Figure 3 12 Connecting the OTDR to Spooled Cable ...
Страница 133: ...Using the ChannelMap Function Running the Test 4 4 3 ajt55f eps Figure 4 2 ChannelMap Test Connections ...
Страница 136: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 4 6 ...
Страница 148: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 4 ajt61f eps Figure 6 2 Changing the Connector Adapter ...
Страница 192: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 48 ...
Страница 196: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 7 4 ajt03f eps Figure 7 2 Using the Visual Fault Locator ...
Страница 254: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 11 36 ...
Страница 256: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 261: ...Loss Test Methods Method A A 2 B B 3 ajt58f eps Figure B 1 Method A A 2 Reference and Test Connections singlemode shown ...
Страница 263: ...B 5 ajt59f eps Figure B 2 Method B A 1 Reference and Test Connections singlemode shown Loss Test Methods Method B A 1 B ...
Страница 265: ...Loss Test Methods Method C A 3 B B 7 ajt60f eps Figure B 3 Method C A 3 Reference and Test Connections singlemode shown ...
Страница 272: ...B 14 OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 274: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook C 2 ...
Страница 282: ...OF 500 OptiFiber Technical Reference Handbook 8 ...