Using the OTDR
Diagnosing OTDR Test Failures
3
3-53
Table 3-7. Diagnosing Faults on OTDR Traces
Large reflective event with high loss (top), excessive tailing (middle), or a hook on the falling edge of
the trace (bottom). May be identified as an end event though it occurs before the end of the cabling.
May be caused by the following:
•
A dirty, scratched, cracked, misaligned, or unseated connector. Misaligned or unseated
connectors can also cause large reflections that produce ghosts. Bad connectors should be
cleaned, repolished, or replaced. A hook, as shown in the bottom example, can occur when a
large reflection causes the OTDR detector’s gain to become non-linear.
•
A good connector with a sharp bend or crack within its deadzone. If the cable is tightly bent the
tester may indicate a break, especially at longer wavelengths or in Manual OTDR mode with
smaller resolution settings. Use a visual fault locator to precisely locate the fault.
•
A crack in the fiber. Use a visual fault locator to precisely locate the fault.
•
A connection between mismatched fibers (different backscatter coefficients, core sizes,
numerical apertures, or other parameters). The top example could be caused by a larger core
(on the left) connected to a smaller core.
-continued-
Содержание OF-500 OptiFiber
Страница 12: ...OF 500 OptiFiber Technical Reference Handbook x ...
Страница 18: ...OF 500 OptiFiber Technical Reference Handbook xvi ...
Страница 27: ...Getting Acquainted Powering the Tester 1 1 9 ajt20f eps Figure 1 1 Battery Pack Features ...
Страница 29: ...Getting Acquainted Verifying Operation 1 1 11 ajt56f eps Figure 1 2 Removing the Module ...
Страница 46: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 1 28 ...
Страница 95: ...Using the OTDR Running the OTDR Test 3 3 21 ajt33f eps Figure 3 12 Connecting the OTDR to Spooled Cable ...
Страница 133: ...Using the ChannelMap Function Running the Test 4 4 3 ajt55f eps Figure 4 2 ChannelMap Test Connections ...
Страница 136: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 4 6 ...
Страница 148: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 4 ajt61f eps Figure 6 2 Changing the Connector Adapter ...
Страница 192: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 6 48 ...
Страница 196: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 7 4 ajt03f eps Figure 7 2 Using the Visual Fault Locator ...
Страница 254: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 11 36 ...
Страница 256: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 261: ...Loss Test Methods Method A A 2 B B 3 ajt58f eps Figure B 1 Method A A 2 Reference and Test Connections singlemode shown ...
Страница 263: ...B 5 ajt59f eps Figure B 2 Method B A 1 Reference and Test Connections singlemode shown Loss Test Methods Method B A 1 B ...
Страница 265: ...Loss Test Methods Method C A 3 B B 7 ajt60f eps Figure B 3 Method C A 3 Reference and Test Connections singlemode shown ...
Страница 272: ...B 14 OF 500 OptiFiber Certifying OTDR Technical Reference Handbook ...
Страница 274: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook C 2 ...
Страница 282: ...OF 500 OptiFiber Technical Reference Handbook 8 ...