Chapter 4 Installation and Wiring
PAGE 4-9
4-5-2 Bank Select Output Signals
OUTPUT Definition with BANK SELECT (TB1-12)
OFF
OUTPUT Definition with BANK SELECT (TB1-12)
ON
Pin No.
Signal
IN/OUT
Description of Function/Usage
TB2-1
WORK OUTPUT BIT 5 OUT-1(NO) Output confirmation of WORK SELECT 5 input selects bit
TB2-2
CF Warning
(Compact Flash)
OUT-2(NO)
ON when the CF card remaining capacity is less than 200MB
Output can be enabled on Firmware ver. 1.310 or later with the
following setting:
System parameter: SYS.032[x1xxxx] 0:Disabled / 1: Enabled
TB2-3
Batch Sequence END
OUT-3(NO)
ON when the fastening operation is at the final stage of the batch
sequence. (Firmware version 1.310 or later)
TB2-4
WORK OUTPUT BIT 0 OUT-4(NO)
Output confirmation of WORK SELECT 0~5 input selects bits. Work
number (parameter number) is set from the WORK select inputs.
Used to confirm proper Work set before fastening starts.
TB2-5
WORK OUTPUT BIT 1 OUT-5(NO)
TB2-6
WORK OUTPUT BIT 4 OUT-12(NO)
TB3-7
WORK OUTPUT BIT 2 OUT-6(NO)
TB3-8
WORK OUTPUT BIT 3 OUT-7(NO)
・
Turn OFF the input signal "BANKSELECT" during fastening operation or when not
using bank select function
·
If using the BANK SELECT Input signal, wait for 20 msec or more after turning the
signal ON, before checking the output signal status.
Pin No.
Signal
IN/OUT
Description of Function/Usage
TB2-1
REJECT[NG]
OUT-1(NO)
Output when the fastening operation ends with a fastening result
falling outside a judgment range.
TB2-2
ACCEPT[OK]
OUT-2(NO)
Output when the fastening operation ends with the fastening results
being within the judgment ranges.
TB2-3
ABNORMAL
OUT-3(NO)
Output when an internal error occurs in the system or during the
fastening operation. (The Abnormal Code is displayed on front
display
– An Abnormal must be RESET before normal operation
may resume)
TB2-4
READY
OUT-4(NO)
Output when the STOP signal is ON and the controller is ready to
start a cycle. This signal is also output after the end of fastening,
regardless of the judgment.
TB2-5
BUSY
OUT-5(NO) Output when the fastening process is in cycle
TB2-6
BYPASS
OUT-12(NO) Output when the controller is in the BYPASS (PROGRAM) mode.
TB3-7
Fastening Result
Data Available
OUT-6(NO) Output when fastening result data is available in the controller.
TB3-8
CF CARD FULL
OUT-7(NO)
Output when capacity of the CF card is less than 1%,
or CF card is not inserted
Caution
Содержание Handheld Nutrunner HFC3000
Страница 2: ...www fec usa com Copyright 2017 FEC AUTOMATION SYSTEMS All Rights Reserved ...
Страница 14: ...Notes ...
Страница 15: ...Chapter 1 Outline PAGE 1 1 Chapter 1 Outline 1 ...
Страница 21: ...Chapter 2 Specifications PAGE 2 1 Chapter 2 Specifications 2 ...
Страница 28: ...Chapter 2 Specifications PAGE 2 8 Blank Page ...
Страница 29: ...Chapter 3 Sysytem Description PAGE 3 1 Chapter 3 System Description 3 ...
Страница 36: ...Chapter 3 System Description PAGE 3 8 Memo ...
Страница 37: ...Chapter 4 Installation and Wiring PAGE 4 1 Chapter 4 Installation Wiring 4 ...
Страница 67: ...Chapter 5 Power Up and Operational Tests PAGE 5 1 Chapter 5 Power Up and Operational Tests 5 ...
Страница 71: ...Chapter 6 Fastening Operation PAGE 6 1 Chapter 6 Fastening Operation 6 ...
Страница 151: ...Chapter 7 Troubleshooting PAGE 7 1 Chapter 7 Troubleshooting 7 ...
Страница 169: ...Chapter 8 Options PAGE 8 1 Chapter 8 Options 8 ...
Страница 181: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 1 Chapter 9 Fieldbus I O Interfaces 9 ...
Страница 207: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 27 9 3 2 Description of the hardware RUN LED ERROR LED CC Link Connector ...
Страница 229: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 49 Blank Page ...
Страница 230: ......
Страница 231: ......