Operating Instructions

Micropilot NMR84

Tank Gauging

BA01453G/00/EN/06.21

71545626

2021-11-04
Valid as of version

01.05.zz (Device firmware)

Содержание Micropilot NMR84

Страница 1: ...Products Solutions Services Operating Instructions Micropilot NMR84 Tank Gauging BA01453G 00 EN 06 21 71545626 2021 11 04 Valid as of version 01 05 zz Device firmware ...

Страница 2: ...Micropilot NMR84 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 ...

Страница 3: ...XA820 and FieldCare 50 8 System integration 53 8 1 Overview of the Device Description files DTM 53 9 Commissioning 54 9 1 Terms related to tank measurement 54 9 2 Initial settings 54 9 3 Configuring the measuring device 57 9 4 Configuring the tank gauging application 59 9 5 Advanced settings 79 9 6 Simulation 79 9 7 Protecting settings from unauthorized access 79 10 Operation 80 10 1 Reading off t...

Страница 4: ...ous or fatal injury CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Alternating current Direct current and alternating current Direct current Ground connection A grounded terminal which as ...

Страница 5: ...s or actions that are forbidden Tip Indicates additional information Reference to documentation Reference to graphic Notice or individual step to be observed 1 2 3 Series of steps Result of a step Visual inspection Operation via operating tool Write protected parameter 1 2 3 Item numbers A B C Views Safety instructions Observe the safety instructions contained in the associated Operating Instructi...

Страница 6: ...tification incoming acceptance and storage to mounting connection operation and commissioning through to troubleshooting maintenance and disposal It also contains a detailed explanation of each individual parameter in the operating menu except the Expert menu The description is aimed at those who work with the device over the entire life cycle and perform specific configurations 1 3 4 Description ...

Страница 7: ...ally explosive flammable poisonous and oxidizing media Measuring devices for use in hazardous areas in hygienic applications or in applications where there is an increased risk due to process pressure are labeled accordingly on the nameplate To ensure that the measuring device remains in proper condition for the operation time Only use the measuring device in full compliance with the data on the n...

Страница 8: ...ns or the facility when the device is used in the hazardous area e g explosion protection Check the nameplate to verify if the device ordered can be put to its intended use in the hazardous area Observe the specifications in the separate supplementary documentation that is an integral part of these instructions 2 5 Product safety This measuring device is designed in accordance with good engineerin...

Страница 9: ...cription 3 1 Product design 1 1 2 2 4 5 3 4 3 A0027766 1 Design of Micropilot NMR84 1 Electronics housing 2 Display and operating module can be operated without opening the cover 3 Process connection flange 4 Planar antenna 5 Antenna extension for antennas 200 mm 8 in ...

Страница 10: ... Center 4 2 Product identification The following options are available for identification of the measuring device Nameplate specifications Extended order code with breakdown of the device features on the delivery note W M Device Viewer www endress com deviceviewer Enter the serial number from the nameplate Endress Hauser Operations App Enter the serial number from the nameplate or scan the matrix ...

Страница 11: ... Permitted ambient temperature Ta 10 Temperature resistance of cable 11 Thread for cable entry 12 Material in contact with process 13 Not used 14 Firmware version 15 Device revision 16 Metrology certification numbers 17 Customized parametrization data 18 Ambient temperature range 19 CE mark C tick mark 20 Additional information on the device version 21 Ingress protection 22 Certificate symbol 23 D...

Страница 12: ...na may be damaged or break away Risk of injury Transport the measuring device to the measuring point in its original packaging or at the process connection Do not fasten lifting devices hoisting slings lifting eyes etc at the housing or the antenna but at the process connection Take into account the mass center of the device in order to avoid unintended tilting Comply with the safety instructions ...

Страница 13: ...using a ball valve or mending pipe segments gaps must not exceed 1 mm 0 04 in The stilling well must be smooth on the inside Average roughness 6 3 µm 0 248 µin Length and number of the holes do not affect the measurement The hole diameter deburred can be 1 7 of the well diameter but should not exceed 30 mm 1 2 in An increase of the pipe diameter is possible if the minimum lengths according to the ...

Страница 14: ...n check m Is the device undamaged visual inspection m Does the device conform to the measuring point specifications For example Process temperature Process pressure refer to the chapter on Material load curves of the Technical Information document Ambient temperature range Measuring range m Are the measuring point identification and labeling correct visual inspection m Is the device adequately pro...

Страница 15: ...nals can be in any of these slots Modules with eight terminals can be in slot B or C The exact assignment of the modules to the slots is dependent on the device version 18 Terminal area E Module HART Ex i IS interface E1 H E2 H Terminal area F Remote display F1 VCC connect to terminal 81 of the remote display F2 Signal B connect to terminal 84 of the remote display F3 Signal A connec t to terminal...

Страница 16: ...n the nameplate Supply voltage High voltage AC power supply Operational value 100 to 240 VAC 15 10 85 to 264 VAC 50 60 Hz Low voltage AC power supply Operational value 65 VAC 20 15 52 to 75 VAC 50 60 Hz Low voltage DC power supply Operational value 24 to 55 VDC 20 15 19 to 64 VDC Power consumption Maximum power varies depending on the configuration of the modules The value shows maximum apparent p...

Страница 17: ...efer to SD01763D The measured value is indicated on the DKX001 and on the local display and operating module simultaneously The operating menu cannot be accessed on both modules at the same time If the operating menu is entered in one of these modules the other module is automatically locked This locking remains active until the menu is closed in the first module back to measured value display 6 1...

Страница 18: ...002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG XPF0002 AABEFEG 71273689 7122xxxx XPF0002 AABEFEG AAAAACDEFEG XPF0002 AAACABADJ AAHAHCHRIJJAJBKP 71023451 71023451 71023451 Cover IOM V1 IOM A RTD IOM D Slot A Slot B Slot C Slot D IO Mod FF Display Display asm Detector Main electr SMS electr 6 7 8 9 10 11 12 5 4 3 2 1 www e ndress com d evi...

Страница 19: ...B3 M M D D A1 A1 X0 M A XP A1 A1 A1 M A XP D A1 A1 A2 M A XP D D A1 A1 B1 M M A XP A1 A1 B2 M M A XP D A1 A2 X0 M A XP A XP A1 A2 A1 M A XP A XP D A1 A2 B1 M A XP A XP M A1 B1 X0 M A IS A1 B1 A1 M A IS D A1 B1 A2 M A IS D D A1 B1 B1 M M A IS A1 B1 B2 M M A IS D A1 B2 X0 M A IS A IS A1 B2 A1 M A IS A IS D A1 B2 B1 M A IS A IS M A1 C2 X0 M A IS A XP A1 C2 A1 M A IS A XP D A1 C2 B1 M A IS A XP M 1 Or...

Страница 20: ... Hauser List of abbreviations used in table Primary Output 040 V1 B1 O Ordering feature T Terminal area 040 Primary Output 050 Secondary IO Analog 060 Secondary IO Digital Ex d XP V1 Sakura V1 M Modbus D Digital A XP Analog Ex d XP A IS Analog Ex i IS ...

Страница 21: ... D B1 A1 X0 V1 A XP B1 A1 A1 V1 A XP D B1 A1 A2 V1 A XP D D B1 A1 B1 V1 M A XP B1 A1 B2 V1 M A XP D B1 A2 X0 V1 A XP A XP B1 A2 A1 V1 A XP A XP D B1 A2 B1 V1 A XP A XP M B1 B1 X0 V1 A IS B1 B1 A1 V1 A IS D B1 B1 A2 V1 A IS D D B1 B1 B1 V1 M A IS B1 B1 B2 V1 M A IS D B1 B2 X0 V1 A IS A IS B1 B2 A1 V1 A IS A IS D B1 B2 B1 V1 A IS A IS M B1 C2 X0 V1 A IS A XP B1 C2 A1 V1 A IS A XP D B1 C2 B1 V1 A IS ...

Страница 22: ...er List of abbreviations used in table Primary Output 040 WM550 C1 O Ordering feature T Terminal area 040 Primary Output 050 Secondary IO Analog 060 Secondary IO Digital Ex d XP WM550 Whessoe WM550 D Digital M Modbus A XP Analog Ex d XP A IS Analog Ex i IS ...

Страница 23: ...50 WM550 C1 X0 E2 WM550 WM550 D C1 X0 E3 WM550 WM550 D D C1 A1 X0 WM550 A XP C1 A1 A1 WM550 A XP D C1 A1 A2 WM550 A XP D D C1 A1 B1 WM550 M A XP C1 A1 B2 WM550 M A XP D C1 A1 E1 WM550 WM550 A XP C1 A1 E2 WM550 WM550 A XP D C1 A2 X0 WM550 A XP A XP C1 A2 A1 WM550 A XP A XP D C1 A2 B1 WM550 A XP A XP M C1 A2 E1 WM550 A XP A XP WM550 C1 B1 X0 WM550 A IS C1 B1 A1 WM550 A IS D C1 B1 A2 WM550 A IS D D C...

Страница 24: ...M550 A IS A XP C1 C2 A1 WM550 A IS A XP D C1 C2 B1 WM550 A IS A XP M C1 C2 E1 WM550 A IS A XP WM550 1 Ordering feature 2 Terminal area 3 Primary Output 4 Secondary IO Analog 5 Secondary IO Digital Ex d XP List of abbreviations used in table Primary Output 040 4 20mA HART Ex d E1 O Ordering feature T Terminal area 040 Primary Output 050 Secondary IO Analog 060 Secondary IO Digital Ex d XP M Modbus ...

Страница 25: ... XP A XP E1 A1 A1 A XP A XP D E1 A1 A2 D A XP A XP D E1 A1 B1 M A XP A XP E1 A1 B2 M A XP A XP D E1 B1 X0 A XP A IS E1 B1 A1 A XP A IS D E1 B1 A2 D A XP A IS D E1 B1 B1 M A XP A IS E1 B1 B2 M A XP A IS D 1 Ordering feature 2 Terminal area 3 Primary Output 4 Secondary IO Analog 5 Secondary IO Digital Ex d XP List of abbreviations used in table Primary Output 040 4 20mA HART Ex i H1 O Ordering featu...

Страница 26: ... IS H1 X0 A1 A IS D H1 X0 A2 A IS D D H1 X0 A3 D A IS D D H1 X0 B1 M A IS H1 X0 B2 M A IS D H1 X0 B3 M A IS D D H1 A1 X0 A IS A XP H1 A1 A1 A IS A XP D H1 A1 A2 D A IS A XP D H1 A1 B1 M A IS A XP H1 A1 B2 M A IS A XP D H1 B1 X0 A IS A IS H1 B1 A1 A IS A IS D H1 B1 A2 D A IS A IS D H1 B1 B1 M A IS A IS H1 B1 B2 M A IS A IS D 1 Ordering feature 2 Terminal area 3 Primary Output 4 Secondary IO Analog ...

Страница 27: ...and or V1 or WM550 module may be in different slots of the terminal compartment In the operating menu the Modbus and V1 or WM550 interfaces are designated by the respective slot and the terminals within this slot A1 4 B1 4 C1 4 D1 4 Terminals of the Modbus module Designation of the module in the operating menu Modbus X1 4 X A B C or D X1 1 Terminal name S Description Cable shielding connected via ...

Страница 28: ... Analog I O module Ex d XP or Ex i IS D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER i B 1 2 3 4 5 6 7 8 B1 3 B4 8 C 1 2 3 4 5 6 7 8 C1 3 C4 8 A0031168 Terminal B1 3 Function Analog input or output configurable Passive usage 30 Active usage 32 Designation in the operating menu Analog I O B1 3 138 Terminal C1 3 Function Analog input or output config...

Страница 29: ...Micropilot NMR84 Electrical connection Endress Hauser 29 Terminal C4 8 Function Analog input RTD 33 Designation in the operating menu Analog IP C4 8 132 ...

Страница 30: ...2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER c a b E G F 1 1 3 2 2 4 HR CDI on i C B 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 A0027931 8 Passive usage of the Analog I O module in the output mode a Power supply b HART signal output c Analog signal evaluation Operating mode 4 20mA input or HART master 4 20mA input D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 ...

Страница 31: ...3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER a E G F 1 1 3 2 2 4 HR CDI on i C B 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 b A0027934 10 Passive usage of the Analog I O module in the HART master mode a Power supply b Up to 6 external devices with HART signal output ...

Страница 32: ...5 V 22 mA Output voltage of the Ex ia module 18 5 V 4 mA to 12 5 V 22 mA Operating mode 4 20mA output or HART slave 4 20mA output D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER b a E G F 1 1 3 2 2 4 HR CDI on i C B 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 A0027932 11 Active usage of the Analog I O module in the output mode a HART signal ou...

Страница 33: ... a A0027936 13 Active usage of the Analog I O module in the HART master mode a Up to 6 external devices with HART signal output The maximum current consumption for the connected HART devices is 24 mA i e 4 mA per device if 6 devices are connected 6 1 9 Connection of a RTD A C B 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 A0026371 A 4 wire RTD connection B 3 wire RTD connection C 2 wire RTD con...

Страница 34: ...uts or outputs examples Each Digital IO Module provides two digital inputs or outputs In the operating menu each input or output is designated by the respective slot and two terminals within this slot A1 2 for example denotes terminals 1 and 2 of slot A The same is valid for slots B C and D if they contain a Digital IO module For each of these pairs of terminals one of the following operating mode...

Страница 35: ...lines Screened cable must be used for the 4 to 20 mA signal lines the RTD connection Digital I O signal lines Shielded cable is recommended if using the relays Observe the grounding concept of the plant HART communication line Shielded cable is recommended if using the HART protocol Observe the grounding concept of the plant Modbus communication line Observe the cable conditions from the TIA 485 A...

Страница 36: ...ap A0013960 5 Insert blind plugs appropriate for the safety rating of the device e g Ex d XP 6 4 Post connection check m Are cables or the device undamaged visual inspection m Do the cables comply with the requirements m Do the cables have adequate strain relief m Are all cable glands installed firmly tightened and correctly sealed m Does the supply voltage match the specifications on the transmit...

Страница 37: ...he following interfaces The display and operating module at the device or the remote display and operating module DKX001 39 FieldCare connected through the service interface in the terminal compartment of the device 50 FieldCare connected through Tankvision Tank Scanner NXA820 remote operation 50 FieldCare connected through Commubox FXA195 98 to a HART interface of the device ...

Страница 38: ... Simulation Used to simulate measured values or output values Device check Contains all parameters needed to check the measurement capability of the device Expert 1 Contains all parameters of the device including those which are already contained in one of the other menus This menu is organized according to the function blocks of the device The parameter of the Expert menu are described in GP01071...

Страница 39: ...losed in the first module back to measured value display 7 3 1 Display and operating elements The device has an illuminated liquid crystal display LCD that shows measured and calculated values as well as the device status in the standard view Other views are used to navigate through the operating menu and to set parameter values The device is operated by three optical keys namely and E They are ac...

Страница 40: ... valid A0013959 Function check The device is in service mode e g during a simulation A0013958 Out of specification The device is operated Outside of its technical specifications e g during startup or a cleaning Outside of the configuration carried out by the user e g level outside configured span A0013957 Maintenance required Maintenance is required The measured value is still valid Measured value...

Страница 41: ...ated A0031169 Calibration to regulatory standards disturbed Is displayed in the following situations The write protection switch is OFF 48 The write protection switch is ON but the level value can currently not be guaranteed Locking state symbols Symbol Meaning A0011978 Display parameter Marks display only parameters which cannot be edited A0011979 Device locked In front of a parameter name The de...

Страница 42: ...in the header if you are in the Operation menu A0011974 Setup Is displayed in the main menu next to the selection Setup in the header if you are in the Setup menu A0011976 Expert Is displayed in the main menu next to the selection Expert in the header if you are in the Expert menu A0011977 Diagnostics Is displayed in the main menu next to the selection Diagnostics in the header if you are in the D...

Страница 43: ...el and takes you to the next higher level If help text is open closes the help text of the parameter Pressing the keys for 2 s returns you to the measured value display standard view 7 3 4 Wizard view 2 1 4756 5 mm Mapping Distance unknown Distance Confirm distance A0045876 18 Wizard view on the display module 1 Current wizard 2 Display area for navigation Wizard navigation symbols Symbol Meaning ...

Страница 44: ...n to the left A0013986 Exits the input without applying the changes A0014040 Clears all entered characters Meaning of the keys in the numeric editor Key Meaning A0028324 Minus key In the input mask moves the selection bar to the left backwards A0028325 Plus key In the input mask moves the selection bar to the right forwards A0028326 Enter key Pressing the key briefly adds the selected number to th...

Страница 45: ...e letters For entering numbers For entering special characters A0013985 Confirms selection A0013987 Switches to the selection of the correction tools A0013986 Exits the input without applying the changes A0014040 Clears all entered characters Correction symbols under A0013989 Clears all entered characters A0013991 Moves the input position one position to the right A0013990 Moves the input position...

Страница 46: ... Keypad lock Automatic keypad lock Operation via the local display is automatically locked after a start up or restart of the device if the device has not been operated via the display for 1 minute When attempting to access the operating menu while the keylock is enabled the Keylock on message appears Disabling the keypad lock 1 The keylock is enabled Press for at least 2 seconds A context menu ap...

Страница 47: ...efine access code Define access code 2 Enter the intended access code max 4 digits 3 Repeat the same code in the Confirm access code parameter The user is in the Operator role The symbol appears in front of all write protected parameters Switching to the Maintenance role If the symbol appears on the local display in front of a parameter the parameter is write protected because the user is in the O...

Страница 48: ...2 Unscrew the housing cover 3 Pull out the display module with a gentle rotation movement 4 Using a flat blade screwdriver or a similar tool set the write protection switch WP into the desired position ON operating menu is locked OFF operating menu is unlocked 5 Put the display module onto the connection compartment screw the cover closed and tighten the securing clamp To avoid acces to the write ...

Страница 49: ...1 Indication of the locking state XXXX XXX X X 20 50 XX XX A0015870 22 Write protection symbol in the header of the display Write protection via locking switch is indicated as follows Locking status 124 Hardware locked appears in the header of the display ...

Страница 50: ...he device using the Save Restore function of FieldCare the device must be restarted by the following setting Setup Advanced setup Administration Device reset Restart device This ensures correct operation of the device after the restore 7 5 Access to the operating menu via Tankvision Tank Scanner NXA820 and FieldCare 7 5 1 Wiring scheme NXA820 5 6 4 1 2 3 7 A0025621 24 Connection of Tank Gauging de...

Страница 51: ...e the HART CommDTM NXA is installed and update the DTM catalogue if required 2 Create a new project in FieldCare 3 A0028515 Add a new device NXA HART Communication 4 A0028516 Open the configuration of the DTM and enter the required data IP address of the NXA820 Password hart Tank identification only with NXA V1 05 or higher ...

Страница 52: ...e device can be configured The Save Restore function After a device configuration has been saved to a computer and restored to the device using the Save Restore function of FieldCare the device must be restarted by the following setting Setup Advanced setup Administration Device reset Restart device This ensures correct operation of the device after the restore ...

Страница 53: ...of the Device Description files DTM To integrate the device via HART into FieldCare a Device Description file DTM according to the following specification is required Manufacturer ID 0x11 Device type NMR8x 0x112E HART specification 7 0 DD files For information and files see www endress com ...

Страница 54: ...eight 7 Distance 8 Dipping reference 9 2 Initial settings 9 2 1 Setting the display language Setting the display language via the display module 1 While in the standard view 40 press E If required select Keylock off from the context menu and press E again The Language parameter appears 2 Open the Language parameter and select the display language Setting the display language via an operating tool ...

Страница 55: ...time clock Setting the real time clock via the display module 1 Navigate to Setup Advanced setup Date time Set date 2 Use the following parameters to set the the real time clock to the current date and time Year Month Day Hour Minutes Setting the real time clock via an operating tool e g FieldCare 1 Navigate to Setup Advanced setup Date time 2 Go to the Set date parameter and select the Start opti...

Страница 56: ...Commissioning Micropilot NMR84 56 Endress Hauser 4 Go to the Set date parameter and select the Confirm time option The real time clock is set to the current date and time ...

Страница 57: ...defined 120 The Set level parameter can only be used to compensate for a constant level error To eliminate errors resulting from interference echos use the interference echo suppression map Interference echo suppression map in an operating tool e g FieldCare DeviceCare Navigation path Setup Parameter Meaning Description Setup Distance Shows the measured distance from the lower edge of the device f...

Страница 58: ...o correct the level readings using independently taken hand dips The dip table is used in particular to adapt the level gauge to the specific application conditions such as a mechanical offset and the tank or stilling well design The dip table is managed in the Dip table submenu 205 ...

Страница 59: ...essing in the device Description Linking input values to tank variables 68 Tank calculation Direct Level Measurement 69 Tank calculation Hybrid Tank Measurement System HTMS 70 Tank calculation Correction of the Hydrostatic Tank Deformation HyTD 71 Tank calculation Thermal Tank Shell Correction CTSh 72 Alarms limit evaluation 73 Configuration of the signal output Description 4 20mA output 74 HART s...

Страница 60: ...nal assignment 28 Devices with an address larger than 15 are not recognized by the Micropilot Slot B or C Setting the operating mode of the Analog I O module This section is not relevant for the HART Ex is output Slot E This output always functions as a HART master for the connected HART slaves If HART devices are connected to an Analog I O module slot B or C in the terminal compartment this modul...

Страница 61: ... pressure unit may be selected 4 If the device measures a density Go to the Output density parameter 129 and specify which of the four HART variables contains the measured density Only a HART variable with a density unit may be selected 5 If the device measures a temperature Go to the Output temperature parameter 129 and specify which of the four HART variables contains the measured temperature On...

Страница 62: ...me of the connected Prothermo 2 Go to the Configure device parameter and select Yes 3 a A0030098 27 Prothermo NMT53x Position of the bottom temperature element a Distance from bottom temperature element to zero reference tank bottom or datum plate To configure a Prothermo NMT53x Go to the Bottom point parameter and enter the position of the bottom temperature element see picture above The value en...

Страница 63: ...ter and enter the distance between the physical end of the probe and the zero level value in the tank tank bottom or datum plate The value entered into the Bottom point parameter in the Tank Gauging device is handed over to the End of probe to zero distance parameter in the connected Prothermo NMT8x To check the temperatures measured by the individual elements go to the following submenu Operation...

Страница 64: ... 3 Go to the Operating mode parameter 138 and select 4 20mA input or HART master 4 20mA input 4 Go to the Process variable parameter 144 and specify which process variable is transmitted by the connected device 5 Go to the Analog input 0 value parameter 144 and define which value of the process variable corresponds to an input current of 4 mA see diagram below 6 Go to the Analog input 100 value pa...

Страница 65: ...O module Setup Advanced setup Input output Analog IP X4 8 3 Go to the RTD type parameter 132 and specify the type of the connected RTD 4 A C B 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 A0026371 32 RTD connection types A 4 wire RTD connection B 3 wire RTD connection C 2 wire RTD connection Go to the RTD connection type parameter 133 and specify the type of connection of the RTD 2 3 or 4 wire ...

Страница 66: ...s whether the measured temperature refers to the product or to the gas phase Offset for resistance and or temperature An offset for the resistance or the temperature can be defined in the following submenu Expert Input output Analog IP X4 8 Ohms offset is added to the measured resistance before the calculation of the temperature Temperature offset after conversion is added to the measured temperat...

Страница 67: ...rtant parameters of this submenu are Operating mode and Contact type The Operating mode parameter Setup Advanced setup Input output Digital Xx x Operating mode DIO 2 4 _ 2 4 1 3 1 3 A DIO B A0029262 A Operating mode Input passive B Operating mode Input active Meaning of the options Input passive The DIO module measures the voltage provided by an external source Depending on the status of the exter...

Страница 68: ...tank variable in the following parameters Tank variable Parameter defining the source of this variable Bottom water level Setup Advanced setup Application Tank configuration Level Water level source Average or spot temperature of the product Setup Liquid temp source Setup Advanced setup Application Tank configuration Temperature Liquid temp source Temperature of the air surrounding the tank Setup ...

Страница 69: ...ure are measured directly 1 2 3 1 2 A B A0029255 A Direct level measurement without temperature B Direct level and temperature measurement 1 Level transmitter 2 To inventory management system 3 Temperature transmitter If a temperature transmitter is connected Navigate to Setup Liquid temp source and specify from which device the temperature is obtained ...

Страница 70: ...osition 1 Micropilot 2 To inventory management system 3 Pressure sensor bottom 4 Pressure sensor top 1 Navigate to Setup Advanced setup Application Tank configuration Pressure 2 Go to P1 bottom source 184 and specify from which device the bottom pressure P1 is obtained 3 If a top pressure transmitter P3 is connected Go to P3 top source 186 and specify from which device the top pressure P3 is obtai...

Страница 71: ...ydrostatic pressure exerted by the liquid stored in the tank The compensation is based on a linear approximation obtained from manual hand dips at several levels divided over the full range of the tank A B C D A0028722 34 Correction of the hydrostatic tank deformation HyTD A Distance tank nearly empty B Gauge Reference Height GRH C HyTD correction value D Distance tank filled The Correction of the...

Страница 72: ...nsulation factors for both the dry and wet parts of the wire and the tank shell The temperatures used for the correction can be selected from on manual or measured values This correction is recommended for the following situations if the operating temperature deviates considederably from the temperature during calibration ΔT 10 C 18 F for extremely high tanks for refrigerated cryogenic or heated a...

Страница 73: ...nciple of the limit evaluation A Alarm mode On B Alarm mode Latching 1 HH alarm value 2 H alarm value 3 L alarm value 4 LL alarm value 5 HH alarm 6 H alarm 7 L alarm 8 LL alarm 9 Clear alarm Yes or power off on 10 Hysteresis The limit evaluation is configured in the Alarm 1 to 4 submenus Navigation path Setup Advanced setup Alarm Alarm 1 to 4 For Alarm mode Latching all alarms remain active until ...

Страница 74: ...t source parameter and select the tank variable which is to be transmitted via the 4 20mA output 4 Go to the 0 value parameter and enter the value of the selected tank variable which will be mapped to 4 mA 5 Go to the 100 value parameter and enter the value of the selected tank variable which will be mapped to 20 mA 0 1 100 4mA 2 20mA I mA A0032953 37 Scaling of the tank variable to the output cur...

Страница 75: ...RT variables are transmitted to a connected HART Master Special case PV 4 20mA signal In exceptional cases it might be required that the Primary Variable PV transmits a different tank variable than the 4 20mA output This is configured as follows 1 Navigate to Setup Advanced setup Communication HART output Configuration 2 Go to the PV source parameter and select Custom The following additional para...

Страница 76: ...n of the Modbus output D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER A 1 2 3 4 A1 4 i D 1 2 3 4 D1 4 A0031200 39 Possible locations of the Modbus modules examples depending on the device version these modules may also be in slot B or C 18 The Micropilot NMR8x acts as a Modbus slave Measured or calculated tank values are stored in registers which c...

Страница 77: ...X1 4 Configuration 157 Setup Advanced setup Communication V1 X1 4 V1 input selector 160 9 4 16 Configuration of the WM550 output D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER A 1 2 3 4 A1 4 i D 1 2 3 4 D1 4 A0031200 41 Possible locations of the WM550 modules examples depending on the device version these modules may also be in slot B or C 18 The f...

Страница 78: ...ls within this slot The most important parameters of this submenu are Operating mode Digital input source and Contact type A digital output can be used to output the state of an alarm if an alarm has been configured 73 transmit the status of a digital input if a digital input has been configured 67 To configure a digital output proceed as follows 1 Navigate to Setup Advanced setup Input output Dig...

Страница 79: ...ut For a description refer to 148 9 5 Advanced settings For a more detailed configuration of the signal inputs the tank calculations and the signal outputs refer to the Advanced setup submenu 124 9 6 Simulation To check the correct configuration of the device and of the control system it is possible to simulate different situations measured values diagnostic messages etc See the Simulation submenu...

Страница 80: ... see SIL Safety manual CT active all parameters The custody transfer mode is active 48 WHG locked The device is in WHG locked mode Detailed information on this topic see SIL Safety manual Temporarily locked Write access to the parameters is temporarily lock due to device internal processing e g data upload download reset Once the internal processing has been completed the parameters can be changed...

Страница 81: ... is not connected correctly Connect the plug correctly Display is defective Replace display Display contrast too low Set Setup Advanced setup Display Contrast display to a value 60 Communication error is indicated on the display when starting the device or connecting the display Electromagnetic interference Check grounding of the device Broken display cable or display plug Exchange display CDI com...

Страница 82: ...ements Status signals A0013956 Failure A device error is present The measured value is no longer valid A0013959 Function check The device is in service mode e g during a simulation or a warning A0013958 Out of specification The device is operated Outside of its technical specifications e g during startup or a cleaning Outside of the configuration carried out by the user e g level outside configure...

Страница 83: ... event Diagnostics event Status symbol Status signal Event number Event text Example A0013962 A0013956 441 Curr output 1 3 digit number If two or more diagnostic messages are pending simultaneously only the message with the highest priority is shown Additional pending diagnostic messages can be shown in Diagnostic list submenu 242 Operating elements Operating functions in menu submenu A0013970 Plu...

Страница 84: ... code 5 Operation time of occurrence 6 Remedial measures A diagnostic message appears in the standard view measured value display 1 Press symbol The Diagnostic list submenu opens 2 Select the desired diagnostic event with or and press The message for the remedial measures for the selected diagnostic event opens 3 Press simultaneously The message for the remedial measures closes The user is in the ...

Страница 85: ...44 1 Status area with status signal 2 Diagnostic information 3 Remedial measures with Service ID Furthermore diagnostic events that have occurred can be viewed in the Diagnostic list submenu 11 3 1 Status signals The status signals provide information on the state and reliability of the device by categorizing the cause of the diagnostic information diagnostic event Symbol Meaning A0017271 Failure ...

Страница 86: ...ickly On the home page Remedy information is displayed in a separate field below the diagnostics information In the Diagnostics menu Remedy information can be called up in the working area of the user interface The user is in the Diagnostics menu 1 Call up the desired parameter 2 On the right in the working area mouse over the parameter A tool tip with remedy information for the diagnostic event a...

Страница 87: ...arm 262 Module connection 1 Check module connections 2 Change electronic modules F Alarm 270 Main electronics failure Replace main electronics F Alarm 271 Main electronics failure 1 Restart device 2 Change main electronic module F Alarm 272 Main electronics failure Restart device F Alarm 272 Main electronics failure 1 Restart device 2 Contact service F Alarm 273 Main electronics failure 1 Emergenc...

Страница 88: ...meout AIO 1 to 2 1 Check wiring 2 Change I O module F Alarm 408 Invalid range AIO 1 to 2 1 Check device configuration 2 Check wiring C Warning 409 RTD temp out of range 1 to 2 1 Check electronic modules 2 Change I O or main electronic module C Warning 410 Data transfer 1 Check connection 2 Retry data transfer F Alarm 411 Hart device 1 to 15 has malfunction 1 Check HART device 2 Change HART device ...

Страница 89: ...ce C Warning 508 Vapor temperatur source no longer valid Change input source C Warning 509 Air temperature source no longer valid Change input source C Warning 510 P1 source no longer valid Change input source C Warning 511 P2 source no longer valid Change input source C Warning 512 P3 source no longer valid Change input source C Warning 513 Upper density source no longer valid Change input source...

Страница 90: ...ce no longer valid Change input source C Warning 537 Trend source no longer valid Change input source C Warning 538 HART output PV mA source not valid Change input source C Warning 539 Modbus 1 4 SP source invalid Set valid SP input selector C Warning 540 V1 1 4 SP source invalid Set valid SP input selector C Warning 541 Modbus 1 4 alarm source invalid Set valid alarm input selector C Warning 542 ...

Страница 91: ...no longer valid Change input source C Warning Diagnostic of process 801 Energy too low Increase supply voltage S Warning 803 Current loop 1 Check device configuration 2 Check wiring F Alarm 803 Current loop 1 to 2 M Warning 803 Current loop C Warning 825 System temperature 1 Check ambient temperature 2 Check process temperature S Warning 825 System temperature F Alarm 826 Sensor temperature 1 Chec...

Страница 92: ... to 4 LowLow 1 Check alarm source 2 Check configuration settings C Warning 965 Alarm 1 to 4 HighHigh 1 Check alarm source 2 Check configuration settings F Alarm 966 Alarm 1 to 4 High 1 Check alarm source 2 Check configuration settings F Alarm 967 Alarm 1 to 4 Low 1 Check alarm source 2 Check configuration settings F Alarm 968 Alarm 1 to 4 LowLow 1 Check alarm source 2 Check configuration settings ...

Страница 93: ...tate use the Device reset parameter 237 11 7 Device information Information on the device order code hardware and software version of the individual modules etc can be found in the Device information submenu 243 11 8 Firmware history Date Software version Modifications Documentation NMR84 Operating Instructions Description of Parameters Technical Information 04 2016 01 00 zz Original software BA01...

Страница 94: ...aning the exterior of measuring devices always use cleaning agents that do not attack the surface of the housing or the seals 12 2 Endress Hauser services Endress Hauser offers a wide variety of services for maintenance such as recalibration maintenance service or device tests Your Endress Hauser Sales Center can provide detailed information on the services ...

Страница 95: ...esignation on the nameplate Only replace parts with identical parts Carry out repairs according to the instructions On completion of repairs carry out the specified routine test on the device Only Endress Hauser Service may convert a certified device into a different certified variant Document all repair work and conversions 13 1 3 Replacement of a device or electronic module After a complete devi...

Страница 96: ...ss Hauser offers a wide range of services Your Endress Hauser Sales Center can provide detailed information on the services 13 4 Return The requirements for safe device return can vary depending on the device type and national legislation 1 Refer to the website for more information http www endress com support return material 2 Return the device if repairs or a factory calibration are required or ...

Страница 97: ...8019 45 Weather protection cover dimensions mm in Materials Protection cover and mounting brackets Material 316L 1 4404 Screws and washers Material A4 The weather protection cover can be ordered together with the device Ordering feature 620 Accessory Enclosed option PA Weather Protection Cover It can also be ordered as an accessory Order code 71292751 for NMR8x and NRF8x ...

Страница 98: ...ication protocol of the host system Eliminates vendor lock in for field devices Field communication protocol field device Modbus RS485 Host communication protocol host system Saab TRL 2 1 measuring device per Gauge Emulator Separate power supply 100 to 240 VAC 50 to 60 Hz 0 375 A 15 W Several approvals for the hazardous area 14 3 Service specific accessories Commubox FXA195 HART For intrinsically ...

Страница 99: ...ltage drop for universal use to display 4 to 20 mA HART signals Technical Information TI01043K Tankvision Tank Scanner NXA820 Tankvision Data Concentrator NXA821 Tankvision Host Link NXA822 Inventory Management System with completely integrated software for operation via standard web browser Technical Information TI00419G ...

Страница 100: ...and parametrization some parameters will not be available in a given situation For details refer to the Prerequisite category in the description of the respective parameter The representation essentially corresponds to the menu in an operating tool e g FieldCare On the local display there may be minor differences in the menu structure Details are mentioned in the description of the respective subm...

Страница 101: ...osition 113 Element position 1 to 24 113 Density 113 Observed density 113 Vapor density 113 Air density 114 Measured upper density 114 Measured middle density 114 Measured lower density 114 Pressure 115 P1 bottom 115 P3 top 115 GP values 116 GP 1 to 4 name 116 GP Value 1 116 GP Value 2 116 GP Value 3 116 GP Value 4 117 Setup 118 Device tag 118 Units preset 118 ...

Страница 102: ...20 Present mapping 122 Mapping end point 122 Record map 122 Distance 123 Liquid temp source 123 Advanced setup 124 Locking status 124 User role 124 Enter access code 124 Input output 125 HART devices 125 Number of devices 125 HART Device s 126 Forget device 131 Analog IP 132 Operating mode 132 Thermocouple type 133 RTD type 132 RTD connection type 133 ...

Страница 103: ...5 Maximum probe temperature 136 Probe position 136 Damping factor 137 Gauge current 137 Analog I O 138 Operating mode 138 Current span 139 Fixed current 140 Analog input source 140 Failure mode 141 Error value 142 Input value 142 0 value 142 100 value 143 Input value 143 Output values 143 Process variable 144 Analog input 0 value 144 Analog input 100 value 144 ...

Страница 104: ...HG 146 Expected SIL WHG chain 147 Digital Xx x 148 Operating mode 148 Digital input source 149 Input value 150 Contact type 150 Output simulation 150 Output values 151 Readback value 151 Used for SIL WHG 152 Expected SIL WHG chain 152 Communication 153 Communication interface 1 to 2 Communication interface protocol Configuration 154 Configuration 157 Configuration 161 ...

Страница 105: ...tion 164 Information 172 Application 174 Tank configuration 174 Level 174 Temperature 178 Density 182 Pressure 184 Tank calculation 189 HyTD 191 CTSh 196 HTMS 201 Dip table 208 Alarm 209 Alarm 1 to 4 209 Safety settings 218 Output echo lost 218 Delay time echo lost 218 Safety distance 218 Sensor config 220 Tube diameter 220 ...

Страница 106: ... Echo tracking 222 Evaluation mode 222 History reset 222 Display 223 Language 223 Format display 223 Value 1 to 4 display 224 Decimal places 1 to 4 225 Separator 226 Number format 226 Header 227 Header text 227 Display interval 227 Display damping 228 Backlight 228 Contrast display 228 System units 230 Units preset 118 Distance unit 230 Pressure unit 231 ...

Страница 107: ...Set date 233 Year 233 Month 234 Day 234 Hour 234 Minute 235 SIL confirmation 236 Deactivate SIL WHG 236 Administration 237 Define access code 237 Device reset 237 Diagnostics 239 Actual diagnostics 239 Timestamp 239 Previous diagnostics 239 Timestamp 240 Operating time from restart 240 Operating time 240 Date time 233 ...

Страница 108: ...rmware CRC 244 Weight and measures configuration CRC 244 Device name 244 Order code 244 Extended order code 1 to 3 245 Simulation 246 Device alarm simulation 246 Diagnostic event simulation 246 Simulation distance on 246 Simulation distance 247 Current output 1 simulation 247 Simulation value 247 Device check 249 Start device check 249 Result device check 249 Level signal 249 Near distance 250 ...

Страница 109: ...stance from the zero position tank bottom or datum plate to the product surface Additional information Read access Operator Write access Tank Level Navigation Operation Level Tank Level Description Shows the level as a percentage of the full measuring range Additional information Read access Operator Write access Tank ullage Navigation Operation Level Tank ullage Description Shows the remaining em...

Страница 110: ... tank bottom or datum plate Value is updated when device generates a valid Interface measurement Additional information Read access Maintenance Write access Lower interface level Navigation Operation Level Lower I F level Description Shows measured interface level from zero position tank bottom or datum plate Value is updated when device generates a valid interface measurement Additional informati...

Страница 111: ...e from lower edge of device flange to product surface Additional information Read access Operator Write access 15 2 2 Temperature submenu Navigation Operation Temperature Air temperature Navigation Operation Temperature Air temp Description Shows the air temperature Additional information Read access Operator Write access Liquid temperature Navigation Operation Temperature Liquid temp Description ...

Страница 112: ...es submenu This submenu is only visible if a Prothermo NMT is connected Navigation Operation Temperature NMT elem values Element temperature submenu Navigation Operation Temperature NMT elem values Element temp Element temperature 1 to 24 Navigation Operation Temperature NMT elem values Element temp Element temp 1 to 24 Description Shows the temperature of an element in the NMT Additional informat...

Страница 113: ...rmation Read access Operator Write access 15 2 3 Density submenu Navigation Operation Density Observed density Navigation Operation Density Observed density Description Calculated density of the product Additional information Read access Operator Write access This value is calculated from different measured variables depending on the selected calculation method Vapor density Navigation Operation D...

Страница 114: ...nformation Read access Operator Write access Maintenance Measured upper density Navigation Operation Density Meas upper dens Description Shows the density of the upper phase Additional information Read access Operator Write access Measured middle density Navigation Operation Density Meas middle dens Description Density of the middle phase Additional information Read access Operator Write access Me...

Страница 115: ...gation Operation Pressure P1 bottom Navigation Operation Pressure P1 bottom Description Shows the pressure at the tank bottom Additional information Read access Operator Write access P3 top Navigation Operation Pressure P3 top Description Shows the pressure P3 at the top transmitter Additional information Read access Operator Write access ...

Страница 116: ... information Read access Operator Write access Maintenance GP Value 1 Navigation Operation GP values GP Value 1 Description Displays the value that will be used as general purpose value Additional information Read access Operator Write access GP Value 2 Navigation Operation GP values GP Value 2 Description Displays the value that will be used as general purpose value Additional information Read ac...

Страница 117: ...r 117 Additional information Read access Operator Write access GP Value 4 Navigation Operation GP values GP Value 4 Description Displays the value that will be used as general purpose value Additional information Read access Operator Write access ...

Страница 118: ... Operator Write access Maintenance Units preset Navigation Setup Units preset Description Defines a set of units for length pressure and temperature Selection mm bar C m bar C mm PSI C ft PSI F ft in 16 PSI F ft in 8 PSI F Customer value Factory setting mm bar C Additional information Read access Operator Write access Maintenance If the Customer value option is selected the units are defined in th...

Страница 119: ...e version Additional information Read access Operator Write access Maintenance The reference point is the lower edge of the device flange After changing the Empty parameter 119 the Table mode parameter 208 is automatically set to Disable If Empty 119 has been changed by more than 20 mm 0 8 in it is recommended to delete the dip table The dip table values are not affected by a change of the Empty p...

Страница 120: ...y 0 to 10000 00 mm Factory setting 0 mm Additional information Read access Operator Write access Maintenance The device adjusts the Empty parameter 119 according to the entered value such that the measured level will match the actual level After the change of the Empty parameter 119 the Table mode parameter 208 is automatically set to Disable If Empty has been changed by more than 20 mm 0 8 in it ...

Страница 121: ... device adjusts the signal evaluation and returns to the Confirm distance parameter 120 The distance is recalculated and displayed The comparison must be repeated until the displayed distance matches the actual distance After this the recording of the map can be started by selecting Distance ok option Tank empty To be selected if the tank is completely empty The device records a mapping covering t...

Страница 122: ...ch distance the new mapping has to be recorded Remark Make sure the level signal is not covered by the mapping User entry 100 to 999999 9 mm Factory setting 100 mm Additional information Read access Operator Write access Maintenance Record map Navigation Setup Record map Prerequisite Confirm distance 120 Manual map Description Controls the recording of the map Selection No Record map Overlay map F...

Страница 123: ...urrent envelope curves Factory map The factory map stored in the ROM of the device is used Delete partial map The mapping curve is deleted up to Mapping end point 122 Stop overlay Stops the overlaying of the map Distance Navigation Setup Distance Description Distance from lower edge of device flange to product surface Additional information Read access Operator Write access Liquid temp source Navi...

Страница 124: ...he appropriate access code in Enter access code Temporarily locked SW The device is temporarily locked by processes in the device e g data upload download reset The device will automatically be unlocked after completion of these processes Additional information Read access Operator Write access User role Navigation Setup Advanced setup User role Description Shows the access authorization to the pa...

Страница 125: ...etup Input output HART devices submenu Navigation Setup Advanced setup Input output HART devices Number of devices Navigation Setup Advanced setup Input output HART devices Number devices Description Shows the number of devices on the HART bus Additional information Read access Operator Write access ...

Страница 126: ... Description Shows the name of the transmitter Additional information Read access Operator Write access Polling address Navigation Setup Advanced setup Input output HART devices HART Device s Polling address Description Shows the polling address of the transmitter Additional information Read access Operator Write access Device tag Navigation Setup Advanced setup Input output HART devices HART Devi...

Страница 127: ... TV QV Additional information Read access Operator Write access Maintenance Communication status Navigation Setup Advanced setup Input output HART devices HART Device s Comm status Description Shows the operating status of the transmitter User interface Operating normally Device offline Additional information Read access Operator Write access blank HART PV designation dependent on device Navigatio...

Страница 128: ... other than NMT Operating mode 127 PV SV TV QV Description Shows the third HART variable TV Additional information Read access Operator Write access blank HART QV designation dependent on device Navigation Setup Advanced setup Input output HART devices HART Device s blank Prerequisite For HART devices other than NMT Operating mode 127 PV SV TV QV Description Shows the fourth HART variable QV Addit...

Страница 129: ...asured variables are allocated automatically Description Defines which HART variable is the density Selection No value Primary variable PV Secondary variable SV Tertiary variable TV Quaternary variable QV Factory setting No value Additional information Read access Operator Write access Maintenance Output temperature Navigation Setup Advanced setup Input output HART devices HART Device s Output tem...

Страница 130: ...o value Primary variable PV Secondary variable SV Tertiary variable TV Quaternary variable QV Factory setting No value Additional information Read access Operator Write access Maintenance Output level Navigation Setup Advanced setup Input output HART devices HART Device s Output level Prerequisite Not available for Micropilot S FMR5xx Prothermo NMT53x and Prothermo NMT8x In these cases the measure...

Страница 131: ...ices Forget device Forget device Description With this function an offline device can be deleted from the device list Selection HART Device 1 HART Device 2 HART Device 3 HART Device 4 HART Device 5 HART Device 6 HART Device 7 HART Device 8 HART Device 9 HART Device 10 HART Device 11 HART Device 12 HART Device 13 HART Device 14 HART Device 15 None Factory setting None Additional information Read ac...

Страница 132: ...7 8 C 1 2 3 4 5 6 7 8 C1 3 C4 8 A0032465 46 Terminals for the Analog IP submenu B4 8 or C4 8 respectively Navigation Setup Advanced setup Input output Analog IP Operating mode Navigation Setup Advanced setup Input output Analog IP Operating mode Description Defines the operating mode of the analog input Selection Disabled RTD temperature input Gauge power supply Factory setting Disabled Additional...

Страница 133: ...N43760 Ni1000 617 a 0 00617 DIN43760 Factory setting Pt100 385 a 0 00385 IEC751 Additional information Read access Operator Write access Maintenance Thermocouple type Navigation Setup Advanced setup Input output Analog IP Thermocouple typ Description Defines the type of the connected thermocouple Selection N type B type C type D type J type K type L type L GOST type R type S type T type U type Fac...

Страница 134: ...hows the measured value received via the analog input Additional information Read access Operator Write access Process variable Navigation Setup Advanced setup Input output Analog IP Process variable Prerequisite Operating mode 132 RTD temperature input Description Determines type of measured value Selection Level linearized Temperature Pressure Density Factory setting Level linearized Additional ...

Страница 135: ...igned floating point number Factory setting 0 mm Additional information Read access Operator Write access Maintenance Input value Navigation Setup Advanced setup Input output Analog IP Input value Prerequisite Operating mode 132 Disabled Description Shows the value received via the analog input Additional information Read access Operator Write access Minimum probe temperature Navigation Setup Adva...

Страница 136: ...to 927 C Factory setting 250 C Additional information Read access Operator Write access Maintenance Probe position Navigation Setup Advanced setup Input output Analog IP Probe position Prerequisite Operating mode 132 RTD temperature input Description Position of the temperature probe measured from zero position tank bottom or datum plate This parameter in conjunction with the measured level determ...

Страница 137: ...ing constant in seconds User entry 0 to 999 9 s Factory setting 0 s Additional information Read access Operator Write access Maintenance Gauge current Navigation Setup Advanced setup Input output Analog IP Gauge current Prerequisite Operating mode 132 Gauge power supply Description Shows the current on the power supply line for the connected device Additional information Read access Operator Write...

Страница 138: ...C1 3 respectively Navigation Setup Advanced setup Input output Analog I O Operating mode Navigation Setup Advanced setup Input output Analog I O Operating mode Description Defines the operating mode of the analog I O module Selection Disabled 4 20mA input HART master 4 20mA input HART master 4 20mA output HART slave 4 20mA output Factory setting Disabled Additional information Read access Operator...

Страница 139: ... d module 17 0 V 4 mA to 10 5 V 22 mA Output voltage of the Ex ia module 18 5 V 4 mA to 12 5 V 22 mA Current span Navigation Setup Advanced setup Input output Analog I O Current span Prerequisite Operating mode parameter 138 Disabled option or HART master option Description Defines the current range for the measured value transmission Selection 4 20 mA NE 3 8 20 5 mA 4 20 mA US 3 9 20 8 mA 4 20 mA...

Страница 140: ...ent Prerequisite Current span 139 Fixed current Description Defines the fixed output current User entry 4 to 22 5 mA Factory setting 4 mA Additional information Read access Operator Write access Maintenance Analog input source Navigation Setup Advanced setup Input output Analog I O Analog source Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 139 Fixed curren...

Страница 141: ...1 15 PV 7 HART device 1 15 SV 7 HART device 1 15 TV 7 HART device 1 15 QV 7 Factory setting Tank level Additional information Read access Operator Write access Maintenance Failure mode Navigation Setup Advanced setup Input output Analog I O Failure mode Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Description Defines the output behavior in case of an error Selection Mi...

Страница 142: ...g I O Input value Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 139 Fixed current Description Shows the input value of the analog I O module Additional information Read access Operator Write access 0 value Navigation Setup Advanced setup Input output Analog I O 0 value Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 13...

Страница 143: ...ator Write access Maintenance Input value Navigation Setup Advanced setup Input output Analog I O Input value Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 139 Fixed current Description Shows the output value as a percentage of the complete 4 20mA range Additional information Read access Operator Write access Output value Navigation Setup Advanced setup Inp...

Страница 144: ...nput 0 value Navigation Setup Advanced setup Input output Analog I O AI 0 value Prerequisite Operating mode 138 4 20mA input or HART master 4 20mA input Description Value corresponding to an input current of 0 4mA User entry Signed floating point number Factory setting 0 mm Additional information Read access Operator Write access Maintenance Analog input 100 value Navigation Setup Advanced setup I...

Страница 145: ...Factory setting Warning Additional information Read access Operator Write access Maintenance Process value Navigation Setup Advanced setup Input output Analog I O Process value Prerequisite Operating mode 138 4 20mA input or HART master 4 20mA input Description Shows the input value scaled to customer units Additional information Read access Operator Write access Input value in mA Navigation Setup...

Страница 146: ...O Damping factor Prerequisite Operating mode 138 Disabled or HART master Description Defines the damping constant in seconds User entry 0 to 999 9 s Factory setting 0 s Additional information Read access Operator Write access Maintenance Used for SIL WHG Navigation Setup Advanced setup Input output Analog I O Used for SIL WHG Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA outpu...

Страница 147: ...Expected SIL WHG chain Navigation Setup Advanced setup Input output Analog I O SIL WHG chain Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output The device has a SIL approval Additional information Read access Operator Write access ...

Страница 148: ...es any of these submenus The structure of all these submenus is the same D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER A 1 2 3 4 A1 2 A3 4 i C 1 2 3 4 5 6 7 C1 2 C3 4 A0026424 48 Designation of the digital inputs or outputs examples Navigation Setup Advanced setup Input output Digital Xx x Operating mode Navigation Setup Advanced setup Input outpu...

Страница 149: ... None Additional information Meaning of the options Alarm x any Alarm x High Alarm x HighHigh Alarm x High or HighHigh Alarm x Low Alarm x LowLow Alarm x Low or LowLow The digital output indicates if the selected alarm is currently active The alarms themselves are defined in the Alarm 1 to 4 submenus Digital Xx x 8 The digital signal present at the digital input Xx x is passed through to the digit...

Страница 150: ...erequisite Operating mode 148 Disabled Description Determines the switching behavior of the input or output Selection Normally open Normally closed Factory setting Normally open Output simulation Navigation Setup Advanced setup Input output Digital Xx x Output sim Prerequisite Operating mode 148 Output passive Description Sets the output to a specific simulated value Selection Disable Simulating a...

Страница 151: ...ating inactive Open Open Open Fault 1 Closed Open Open Fault 2 Open Closed Open The Fault 1 and Fault 2 options can be used to check the correct switching behavior of the two relays Output value Navigation Setup Advanced setup Input output Digital Xx x Output values Prerequisite Operating mode 148 Output passive Description Shows the digital output value Additional information Read access Operator...

Страница 152: ...put passive The device has a SIL certificate Description Determines whether the discrete I O module is in SIL WHG mode Selection Enabled Disabled Factory setting Disabled Additional information Read access Operator Write access Maintenance Expected SIL WHG chain Navigation Setup Advanced setup Input output Digital C3 4 SIL WHG chain Prerequisite Operating mode 148 Output passive Additional informa...

Страница 153: ...ice version these modules may also be in slot B or C Navigation Setup Advanced setup Communication Modbus X1 4 V1 X1 4 and WM550 X1 4 submenu This submenu is only present for devices with MODBUS and or V1 and or WM550 option communication interface There is one submenu of this type for each communication interface Navigation Setup Advanced setup Communication Modbus X1 4 Navigation Setup Advanced ...

Страница 154: ... rate of the communication Selection 600 BAUD 1200 BAUD 2400 BAUD 4800 BAUD 9600 BAUD 19200 BAUD Factory setting 9600 BAUD Additional information Read access Operator Write access Maintenance Parity Navigation Setup Advanced setup Communication Modbus X1 4 Configuration Parity Prerequisite Communication interface protocol 153 MODBUS Description Defines the parity of the Modbus communication Select...

Страница 155: ...s X1 4 Configuration Float swap mode Prerequisite Communication interface protocol 153 MODBUS Description Sets the format of how the floating point value is transferred on Modbus Selection Normal 3 2 1 0 Swap 0 1 2 3 WW Swap 1 0 3 2 Factory setting Swap 0 1 2 3 Additional information Read access Operator Write access Maintenance Bus termination Navigation Setup Advanced setup Communication Modbus ...

Страница 156: ...Operating menu Micropilot NMR84 156 Endress Hauser Factory setting Off Additional information Read access Operator Write access Maintenance ...

Страница 157: ...cription Determines which variant of the V1 protocol is used User interface None V1 Factory setting None Additional information Read access Operator Write access Maintenance V1 address Navigation Setup Advanced setup Communication V1 X1 4 Configuration V1 address Prerequisite Communication interface protocol variant 157 V1 Description Identifier of the device for the V1 communication User entry 0 ...

Страница 158: ...l mapping Navigation Setup Advanced setup Communication V1 X1 4 Configuration Level mapping Prerequisite Communication interface protocol 153 V1 Description Determines the transmittable range of levels Selection ve ve ve Factory setting ve Additional information Read access Operator Write access Maintenance In V1 the level is always represented by a number in the range from 0 to 999999 This number...

Страница 159: ...ance Prerequisite Communication interface protocol 153 V1 Description Adjusts the impedance of the communication line User entry 0 to 15 Factory setting 15 Additional information Read access Operator Write access Maintenance The line impedance affects the voltage difference between a logical 0 and a logical 1 on the message of the device to the bus The default setting is suitable for most applicat...

Страница 160: ...4 any Alarm 1 4 HighHigh Alarm 1 4 High or HighHigh Alarm 1 4 High Alarm 1 4 Low Alarm 1 4 Low or LowLow Alarm 1 4 LowLow Factory setting None Additional information Read access Operator Write access Maintenance Alarm 2 input source Navigation Setup Advanced setup Communication V1 X1 4 V1 input select Alarm2 input src Description Determines which discrete value will be transmitted as V1 alarm 2 st...

Страница 161: ...aintenance Configuration submenu This submenu is only present for devices with a WM550 option communication interface Navigation Setup Advanced setup Communication WM550 X1 4 Configuration Baudrate Navigation Setup Advanced setup Communication WM550 X1 4 Configuration Baudrate Prerequisite Communication interface protocol 153 WM550 option Description Defines the baud rate of the WM550 communicatio...

Страница 162: ...ed information on content for WM550 Task 32 Special Documentation SD02567G User entry 0 to 9999 Factory setting 2000 WM550 input selector submenu This submenu is only present for devices with a WM550 option communication interface Navigation Setup Advanced setup Communication WM550 X1 4 WM550 inp select Discrete 1 selector Navigation Setup Advanced setup Communication WM550 X1 4 WM550 inp select D...

Страница 163: ...ng menu Endress Hauser 163 Alarm 1 4 High or HighHigh Alarm 1 4 High Alarm 1 4 Low Alarm 1 4 Low or LowLow Alarm 1 4 LowLow Digital Xx x Factory setting None Additional information Read access Operator Write access Maintenance ...

Страница 164: ... 0 to 63 Factory setting 15 Additional information Read access Operator Write access Maintenance No of preambles Navigation Setup Advanced setup Communication HART output Configuration No of preambles Description Defines the number of preambles in the HART telegram User entry 5 to 20 Factory setting 5 Additional information Read access Operator Write access Maintenance PV source Navigation Setup A...

Страница 165: ... variable PV Additional information The assigned measured variable is also used by the current output Selection None Tank level Tank ullage Measured level Distance Displacer position Water level Upper interface level Lower interface level Bottom level Tank reference height Liquid temperature Vapor temperature Air temperature Observed density value Average profile density Upper density Middle densi...

Страница 166: ...ariable PV User entry Signed floating point number Factory setting 0 mm Additional information Read access Operator Write access Maintenance 100 value Navigation Setup Advanced setup Communication HART output Configuration 100 value Prerequisite PV source Custom Description 100 value of the primary variable PV User entry Signed floating point number Factory setting 0 mm Additional information Read...

Страница 167: ...mary HART variable PV Additional information Read access Operator Write access Percent of range Navigation Setup Advanced setup Communication HART output Configuration Percent of range Description Shows the value of the primary variable PV as a percentage of the defined 0 to 100 range Additional information Read access Operator Write access Assign SV Navigation Setup Advanced setup Communication H...

Страница 168: ...1 bottom P2 middle P3 top GP 1 value GP 2 value GP 3 value GP 4 value Factory setting Liquid temperature Additional information Read access Operator Write access Maintenance The Measured level option doesn t contain a unit If a unit is needed select the Tank level option Secondary variable SV Navigation Setup Advanced setup Communication HART output Configuration Second var SV Prerequisite Assign ...

Страница 169: ...emperature Vapor temperature Air temperature Observed density value Average profile density Upper density Middle density Lower density P1 bottom P2 middle P3 top GP 1 value GP 2 value GP 3 value GP 4 value Factory setting Water level Additional information Read access Operator Write access Maintenance The Measured level option doesn t contain a unit If a unit is needed select the Tank level option...

Страница 170: ...tance Displacer position Water level Upper interface level Lower interface level Bottom level Tank reference height Liquid temperature Vapor temperature Air temperature Observed density value Average profile density Upper density Middle density Lower density P1 bottom P2 middle P3 top GP 1 value GP 2 value GP 3 value GP 4 value Factory setting Observed density value Additional information Read acc...

Страница 171: ...ternary variable QV Navigation Setup Advanced setup Communication HART output Configuration Quaterna var QV Prerequisite Assign QV 170 None Description Shows the value of the fourth HART variable QV Additional information Read access Operator Write access ...

Страница 172: ...NMR8x Additional information Read access Operator Write access Maintenance Device tag Navigation Setup Advanced setup Communication HART output Information Device tag Description Enter a unique name for the measuring point to identify the device quickly within the plant User entry Character string comprising numbers letters and special characters 32 Factory setting NMR8x Additional information Rea...

Страница 173: ...s Allowed characters A Z 0 9 certain special characters User entry Character string comprising numbers letters and special characters 32 Factory setting NMR8x Additional information Read access Operator Write access Maintenance HART date code Navigation Setup Advanced setup Communication HART output Information HART date code Description Enter date of the last configuration change Use this format ...

Страница 174: ...e version Additional information Read access Operator Write access Maintenance The reference point is the lower edge of the device flange After changing the Empty parameter 119 the Table mode parameter 208 is automatically set to Disable If Empty 119 has been changed by more than 20 mm 0 8 in it is recommended to delete the dip table The dip table values are not affected by a change of the Empty p...

Страница 175: ...rrect level into this parameter User entry 0 to 10000 00 mm Factory setting 0 mm Additional information Read access Operator Write access Maintenance The device adjusts the Empty parameter 119 according to the entered value such that the measured level will match the actual level After the change of the Empty parameter 119 the Table mode parameter 208 is automatically set to Disable If Empty has b...

Страница 176: ...el User entry 2000 to 5000 mm Factory setting 0 mm Additional information Read access Operator Write access Maintenance Water level Navigation Setup Advanced setup Application Tank config Level Water level Description Shows the bottom water level Additional information Read access Operator Write access Blocking distance Navigation Setup Advanced setup Application Tank config Level Blocking dist De...

Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...

Страница 178: ...lection Manual value HART device 1 15 temperature AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance Manual liquid temperature Navigation Setup Advanced setup Application Tank config Temperature Man liquid temp Prerequisite Liquid temp source 123 Manual value Description Defines the manual va...

Страница 179: ...Defines source from which the air temperature is obtained Selection Manual value HART device 1 15 temperature AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance Manual air temperature Navigation Setup Advanced setup Application Tank config Temperature Manual air temp Prerequisite Air temperat...

Страница 180: ...hich the vapor temperature is obtained Selection Manual value HART device 1 15 vapor temp AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance Manual vapor temperature Navigation Setup Advanced setup Application Tank config Temperature Man vapor temp Prerequisite Vapor temp source 180 Manual va...

Страница 181: ... menu Endress Hauser 181 Vapor temperature Navigation Setup Advanced setup Application Tank config Temperature Vapor temp Description Shows the measured vapor temperature Additional information Read access Operator Write access ...

Страница 182: ...y setting Dependent on the device version Additional information Read access Operator Write access Maintenance Observed density Navigation Setup Advanced setup Application Tank config Density Observed density Description Shows the measured or calculated density Additional information Read access Operator Write access Air density Navigation Setup Advanced setup Application Tank config Density Air d...

Страница 183: ...ite access Maintenance Vapor density Navigation Setup Advanced setup Application Tank config Density Vapor density Description Defines the density of the gas phase in the tank User entry 0 0 to 500 0 kg m Factory setting 1 2 kg m Additional information Read access Operator Write access Maintenance ...

Страница 184: ...8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance P1 bottom Navigation Setup Advanced setup Application Tank config Pressure P1 bottom Description Shows the pressure at the tank bottom Additional information Read access Operator Write access P1 bottom manual pressure Navigation Setup Advanced setup Application Tank config Press...

Страница 185: ...ad access Operator Write access Maintenance P1 offset Navigation Setup Advanced setup Application Tank config Pressure P1 offset Description Offset for the bottom pressure P1 The offset is added to the measured pressure prior to any tank calculation User entry 25 to 25 bar Factory setting 0 bar Additional information Read access Operator Write access Maintenance P1 absolute gauge Navigation Setup ...

Страница 186: ...e AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance P3 top Navigation Setup Advanced setup Application Tank config Pressure P3 top Description Shows the pressure P3 at the top transmitter Additional information Read access Operator Write access P3 top manual pressure Navigation Setup Advanced setup Application Tank config Pressure P3 t...

Страница 187: ... access Operator Write access Maintenance P3 offset Navigation Setup Advanced setup Application Tank config Pressure P3 offset Description Offset for the top pressure P3 The offset is added to the measured pressure prior to any tank calculation User entry 2 5 to 2 5 bar Factory setting 0 bar Additional information Read access Operator Write access Maintenance P3 absolute gauge Navigation Setup Adv...

Страница 188: ...rite access Maintenance Ambient pressure Navigation Setup Advanced setup Application Tank config Pressure Ambient pressure Description Defines the manual value of the ambient pressure User entry 0 to 2 5 bar Factory setting 1 bar Additional information Read access Operator Write access Maintenance ...

Страница 189: ... to bulging of the tank shell caused by the hydrostatic pressure exerted by the liquid stored in the tank The compensation is based on a linear approximation obtained from manual hand dips at several levels distributed over the full range of the tank A B C D A0028722 52 Correction of the hydrostatic tank deformation HyTD A Distance level below L0 HyTD correction value 0 B Gauge Reference Height GR...

Страница 190: ...pared to the measured level a simple straight line method can be used with good results H 2 1 L L0 3 A0028724 53 Calculation of the HyTD correction 1 Linear correction according to Deformation factor 192 2 Real correction 3 Starting level 191 L Measured level 111 H HyTD correction value 191 Calculation of the HyTD correction L L0 C 0 HyTD C L L x D HyTD 0 L L0 A0028715 L Measured level L0 Starting...

Страница 191: ...igation Setup Advanced setup Application Tank calculation HyTD HyTD mode Description Activates or deactivates the calculation of the Hydrostatic Tank Deformation Selection No Yes Factory setting No Additional information Read access Operator Write access Maintenance Starting level Navigation Setup Advanced setup Application Tank calculation HyTD Starting level Description Defines the starting leve...

Страница 192: ... Setup Advanced setup Application Tank calculation HyTD Deform factor Description Defines the deformation factor for the HyTD change of device position per change of level User entry 1 0 to 1 0 Factory setting 0 2 Additional information Read access Operator Write access Maintenance ...

Страница 193: ... for both the dry and wet parts of the wire and the tank shell The temperatures used for the correction can be selected from on manual or measured values This correction is recommended for the following situations if the operating temperature deviates considederably from the temperature during calibration ΔT 10 C 18 F for extremely high tanks for refrigerated cryogenic or heated applications As th...

Страница 194: ...ure atmosphere surrounding the tank CTSh Calculation of the wall temperature Depending on the parameters Covered tank 196 and Stilling well 197 the temperatures TW of the wetted and TD of the dry part of the tank wall are calculated as follows Covered tank 196 Stilling well 197 TW TD Covered Yes 1 TP TV No 7 8 TP 1 8 TA 1 2 TV 1 2 TA Open top Yes TP TA No 7 8 TP 1 8 TA TA 1 This option is also val...

Страница 195: ...5 Insulated tank Covered tank 196 Open top Stilling well 197 Yes CTSh Calculation of the correction C H L T T L T T CTSh D cal W cal α α A0028716 H Gauge Reference Height L Measured level TD Temperature of the dry part of the tank shell calculated from TP TV and TA TW Temperature of the wetted part of the tank shell calculated from TP TV and TA Tcal Temperature at which the measurement has been ca...

Страница 196: ...Operator Write access CTSh mode Navigation Setup Advanced setup Application Tank calculation CTSh CTSh mode Description Activates or deactivates the CTSh Selection No Yes With wire Only wire Factory setting No Additional information Read access Operator Write access Maintenance Covered tank Navigation Setup Advanced setup Application Tank calculation CTSh Covered tank Description Determines whethe...

Страница 197: ...g No Additional information Read access Operator Write access Maintenance Calibration temperature Navigation Setup Advanced setup Application Tank calculation CTSh Calibration temp Description Specify temperature at which the measurement has been calibrated User entry 50 to 250 C Factory setting 25 C Additional information Read access Operator Write access Maintenance Linear expansion coefficient ...

Страница 198: ...tor Write access Maintenance Wire expansion coefficient Navigation Setup Advanced setup Application Tank calculation CTSh Wire exp coeff Description Defines the expansion coefficient of the wire material of the drum Value is programmed in factory User entry 0 to 100 ppm Factory setting 15 ppm ...

Страница 199: ...ure Setup Advanced setup Tank configuration Pressure P1 bottom HP1 Position of P1 transmitter Setup Advanced setup Tank configuration Pressure P1 position P3 Top pressure Setup Advanced setup Tank configuration Pressure P3 top HP3 Position of P3 transmitter Setup Advanced setup Tank configuration Pressure P3 position ρP Density of the product 1 Measured value Setup Advanced setup Calculation HTMS ...

Страница 200: ...a minimum thickness Δ Δ P P min A0028864 This is equivalent to the following condition for the product level L V H L P P P D min min 1 A0028863 Lmin is defined in the Minimum level parameter 202 As can be seen from the formula it always must be bigger than HP1 If LP V falls below this limit the density is calculated as follows If a previous calculated value is available this value will be kept as ...

Страница 201: ... Description Defines the HTMS mode Depending on the mode one or two pressure transmitters are used Selection HTMS P1 HTMS P1 P3 Factory setting HTMS P1 Additional information Read access Operator Write access Maintenance Meaning of the options HTMS P1 Only a bottom pressure transmitter P1 is used HTMS P1 P3 A bottom P1 and top P3 pressure transmitter are used This option should be selected for pre...

Страница 202: ...on Defines the minimum product level for a HTMS calculation If Lp V falls below the limit defined in this parameter the density retains its last value or the manual value is used instead User entry 0 to 20000 mm Factory setting 7000 mm Additional information Read access Operator Write access Maintenance Minimum pressure Navigation Setup Advanced setup Application Tank calculation HTMS Min pressure...

Страница 203: ...Additional information Read access Operator Write access Maintenance Hysteresis Navigation Setup Advanced setup Application Tank calculation HTMS Hysteresis Description Defines the hysteresis for the HTMS calculation Prevents constant switching if the level is near the switch over point User entry 0 to 2000 mm Factory setting 50 mm Additional information Read access Operator Write access Maintenan...

Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...

Страница 205: ...119 has been changed by more than 20 mm 0 8 in it is recommended to delete the dip table The dip table values are not affected by a change of the Empty parameter 119 Semiautomatic creation of a dip table In order not to mix up measurement values corrected by the dip table with uncorrected measurement values it is recommended to enter new data pairs semiautomatically into the table This means the u...

Страница 206: ...964 1 5 4 3 1 0 0 0 0 0 1 0 0 0 0 0 Dip Table Di Dip Table De Edit table N A0045873 4 Press E to open the line 5 Use to select the cell you want to edit 13964 1 5 4 3 1 0 0 0 0 0 1 0 0 0 0 0 Edit table N Dip Table Di Dip Table De A0045874 6 Press E to open the cell 7 Enter the required number 44 8 Continue until all required table points have been entered 9 Press and simultaneously to quit the tab...

Страница 207: ...itten from the editor to the device in the manual mode 1 1 A0029162 1 Table icon calls up the table editor Open the table editor by clicking on the table icon The graphical table editor appears A0029161 2 If the device already contains a dip table Click Read to load it into the editor 3 Enter or change table values in the table on the right A graphical representation of the table is shown in the d...

Страница 208: ...ss Maintenance Meaning of the options Manual Both the device level and the dip level for each table point have to be entered manually Semiautomatic The device level of each table point is measured by the device itself the corresponding dip level must be entered manually Clear table Deletes the complete dip table Sort table Sorts the table points into an ascending order This must be performed if ta...

Страница 209: ...ced setup Application Alarm Alarm submenu Navigation Setup Advanced setup Application Alarm Alarm Alarm Alarm mode 210 Error value 211 Alarm value source 212 Alarm value 213 HH alarm value 213 H alarm value 213 L alarm value 214 LL alarm value 214 HH alarm 214 H alarm 215 HH H alarm 215 L alarm 215 LL alarm 215 LL L alarm 216 Any error 216 Clear alarm 216 ...

Страница 210: ...f the selected alarm Selection Off On Latching Factory setting Off Additional information Read access Operator Write access Maintenance Meaning of the options Off No alarms are generated On An alarm disappears if the alarm condition is no longer present taking into consideration the hysteresis Latching All alarms remain active until the user selects Clear alarm 216 Yes or the power is switched off...

Страница 211: ...214 5 HH alarm 214 6 H alarm 215 7 L alarm 215 8 LL alarm 215 9 Clear alarm 216 Yes or power off on 10 Hysteresis 217 Error value Navigation Setup Advanced setup Application Alarm Alarm Error value Prerequisite Alarm mode 210 Off Description Defines the alarm to be issued if the input value is invalid Selection No alarm HH H alarm H alarm L alarm LL L alarm All alarms Factory setting All alarms Ad...

Страница 212: ... density Middle density Upper density Correction Tank level GP 1 4 value Measured level P3 position Tank reference height Local gravity P1 position Manual density Tank ullage Average profile density Lower density Upper interface level Lower interface level Bottom level Displacer position HART device 1 15 PV HART device 1 15 SV HART device 1 15 TV HART device 1 15 QV HART device 1 15 PV mA HART dev...

Страница 213: ...ue Navigation Setup Advanced setup Application Alarm Alarm HH alarm value Prerequisite Alarm mode 210 Off Description Defines the high high HH limit value User entry Signed floating point number Factory setting 0 None Additional information Read access Operator Write access Maintenance H alarm value Navigation Setup Advanced setup Application Alarm Alarm H alarm value Prerequisite Alarm mode 210 O...

Страница 214: ...Maintenance LL alarm value Navigation Setup Advanced setup Application Alarm Alarm LL alarm value Prerequisite Alarm mode 210 Off Description Defines the low low LL limit value User entry Signed floating point number Factory setting 0 None Additional information Read access Operator Write access Maintenance HH alarm Navigation Setup Advanced setup Application Alarm Alarm HH alarm Prerequisite Alar...

Страница 215: ...H alarm Prerequisite Alarm mode 210 Off Description Shows whether an HH or H alarm is currently active Additional information Read access Operator Write access L alarm Navigation Setup Advanced setup Application Alarm Alarm L alarm Prerequisite Alarm mode 210 Off Description Shows whether an L alarm is currently active Additional information Read access Operator Write access LL alarm Navigation Se...

Страница 216: ...ny error Navigation Setup Advanced setup Application Alarm Alarm Any error Prerequisite Alarm mode 210 Off Description Show whether any alarm is currently active User interface Unknown Inactive Active Error Factory setting Unknown Additional information Read access Operator Write access Clear alarm Navigation Setup Advanced setup Application Alarm Alarm Clear alarm Prerequisite Alarm mode 210 Latc...

Страница 217: ...alues The hystersis prevents constant changes of the alarm state if the level is near one of the limit values User entry Signed floating point number Factory setting 0 001 Additional information Read access Maintenance Write access Maintenance Damping factor Navigation Setup Advanced setup Application Alarm Alarm Damping factor Description Defines the damping constant in seconds User entry 0 to 99...

Страница 218: ...the echo is kept Alarm The device generates an alarm Delay time echo lost Navigation Setup Advanced setup Safety settings Delay echo lost Description Time between the echo loss and the reaction defined for the output User entry 0 to 99999 9 s Factory setting 60 0 s Additional information Read access Operator Write access Maintenance Safety distance Navigation Setup Advanced setup Safety settings S...

Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...

Страница 220: ...perator Write access Maintenance Information submenu Navigation Setup Advanced setup Sensor config Information Signal quality Navigation Setup Advanced setup Sensor config Information Signal quality Description Shows the quality of the evaluated level signal Additional information Read access Operator Write access Absolute echo amplitude Navigation Setup Advanced setup Sensor config Information Ab...

Страница 221: ...Shows the relative amplitude i e the distance to the evaluation curve of the evaluated level signal Additional information Read access Operator Write access Distance Navigation Setup Advanced setup Sensor config Information Distance Description Distance from lower edge of device flange to product surface Additional information Read access Operator Write access ...

Страница 222: ...tory In addition to the static algorithms a dynamic echo trace is continuously generated and evaluated History off The envelope curve is evaluated only statically History reset Navigation Setup Advanced setup Sensor config Echo tracking History reset Description Resets the history of the echo tracking Selection Reset done Restart echo tracking Delete history Factory setting Reset done Additional i...

Страница 223: ...lish Deutsch русский язык Russian 日本語 Japanese Factory setting English Additional information Read access Operator Write access Operator Format display Navigation Setup Advanced setup Display Format display Prerequisite The device has a local display Description Select how measured values are shown on the display Selection 1 value max size 1 bargraph 1 value 2 values 1 value large 2 values 4 value...

Страница 224: ...8 63 Format display 4 values Read access Operator Write access Operator The Value 1 to 4 display 224 parameters specify which measured values are shown on the display and in which order If more measured values are specified than the current display mode permits the values alternate on the device display The display time until the next change is configured in the Display interval parameter 227 Valu...

Страница 225: ...10 Gauge status 10 AIO B1 3 value 10 AIO B1 3 value mA 10 AIO B1 3 value 10 AIO C1 3 value 10 AIO C1 3 value mA 10 AIO C1 3 value 10 AIP B4 8 value 10 AIP B4 8 value mA 10 AIP B4 8 value 10 AIP C4 8 value 10 AIP C4 8 value mA 10 AIP C4 8 value 10 Factory setting Depending on device version Additional information Read access Operator Write access Maintenance Decimal places 1 to 4 Navigation Setup A...

Страница 226: ...he device has a local display Description Select decimal separator for displaying numerical values Selection Factory setting Additional information Read access Operator Write access Maintenance Number format Navigation Setup Advanced setup Display Number format Prerequisite The device has a local display Description Choose number format for the display Selection Decimal ft in 1 16 Factory setting ...

Страница 227: ... parameter 118 Free text The header contents is defined in the Header text parameter 227 Header text Navigation Setup Advanced setup Display Header text Prerequisite Header 227 Free text Description Enter display header text User entry Character string comprising numbers letters and special characters 11 Factory setting TG Platform Additional information Read access Operator Write access Maintenan...

Страница 228: ...ations in the measured value User entry 0 0 to 999 9 s Factory setting 0 0 s Additional information Read access Operator Write access Maintenance Backlight Navigation Setup Advanced setup Display Backlight Prerequisite The device has a local display Description Switch the local display backlight on and off Selection Disable Enable Factory setting Enable Additional information Read access Operator ...

Страница 229: ...Micropilot NMR84 Operating menu Endress Hauser 229 User entry 20 to 80 Factory setting 30 Additional information Read access Operator Write access Operator ...

Страница 230: ...al information Read access Operator Write access Maintenance If the Customer value option is selected the units are defined in the following parameters In any other case these are read only parameters used to indicate the respective unit Distance unit 230 Pressure unit 231 Temperature unit 231 Distance unit Navigation Setup Advanced setup System units Distance unit Description Select distance unit...

Страница 231: ...aintenance if Units preset 118 Customer value Temperature unit Navigation Setup Advanced setup System units Temperature unit Description Select temperature unit Selection SI units C K US units F R Factory setting C Additional information Read access Operator Write access Maintenance if Units preset 118 Customer value Density unit Navigation Setup Advanced setup System units Density unit Descriptio...

Страница 232: ...Operating menu Micropilot NMR84 232 Endress Hauser Additional information Read access Operator Write access Maintenance if Units preset 118 Customer value ...

Страница 233: ...e time Set date Description Controls the setting of the real time clock Selection Please select Abort Start Confirm time Factory setting Please select Additional information Read access Operator Write access Maintenance Meaning of the options Please select Prompts the user to select an action Abort Discards the entered date and time Start Starts the setting of the real time clock Confirm time Sets...

Страница 234: ... Set date 233 Start Description Enter the current month User entry 1 to 12 Factory setting 1 Additional information Read access Operator Write access Maintenance Day Navigation Setup Advanced setup Date time Day Prerequisite Set date 233 Start Description Enter the current day User entry 1 to 31 Factory setting 1 Additional information Read access Operator Write access Maintenance Hour Navigation ...

Страница 235: ...ry setting 0 Additional information Read access Operator Write access Maintenance Minute Navigation Setup Advanced setup Date time Minute Prerequisite Set date 233 Start Description Enter the current minute User entry 0 to 59 Factory setting 0 Additional information Read access Operator Write access Maintenance ...

Страница 236: ...ich describes the locking procedure and the parameters of this wizard Navigation Setup Advanced setup SIL confirmation Deactivate SIL WHG wizard The Deactivate SIL WHG wizard is only available for devices with SIL or WHG approval Feature 590 Additional Approval option LA SIL or LC WHG overfill prevention which are currently in the SIL or WHG locked state The Deactivate SIL WHG wizard is required t...

Страница 237: ... write protection affects all parameters marked with the symbol in this document Once the access code has been defined write protected parameters can only be modified if the access code is entered in the Enter access code parameter 124 Device reset Navigation Setup Advanced setup Administration Device reset Description Reset the device configuration either entirely or in part to a defined state Se...

Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...

Страница 239: ...everal messages are active at the same time the messages with the highest priority is displayed Information on what is causing the message and remedy measures can be viewed via the symbol on the display Timestamp Navigation Diagnostics Timestamp Description Displays the timestamp for the currently active diagnostic message Additional information Read access Operator Write access Previous diagnosti...

Страница 240: ...the display Timestamp Navigation Diagnostics Timestamp Description Shows the timestamp of the previous diagnostic message Additional information Read access Operator Write access Operating time from restart Navigation Diagnostics Time fr restart Description Shows the time the device has been in operation since the last device restart Additional information Read access Operator Write access Operati...

Страница 241: ...ropilot NMR84 Operating menu Endress Hauser 241 Date time Navigation Diagnostics Date time Description Displays the device internal real time clock Additional information Read access Operator Write access ...

Страница 242: ...t Diagnostics 1 to 5 Description Display the current diagnostics messages with the highest to fifth highest priority Additional information The display consists of Symbol for event behavior Code for diagnostic behavior Operating time of occurrence Event text Timestamp 1 to 5 Navigation Diagnostics Diagnostic list Timestamp 1 to 5 Description Timestamp of the diagnostic message ...

Страница 243: ...d access Operator Write access Serial number Navigation Diagnostics Device info Serial number Description The serial number is a unique alphanumerical code identifying the device It is printed on the nameplate In combination with the Operations app it allows to access all device related documentation Additional information Read access Operator Write access Firmware version Navigation Diagnostics D...

Страница 244: ...escription Result of the cyclic redundancy check of the weights and measure relevant parameters Additional information Read access Operator Write access Device name Navigation Diagnostics Device info Device name Description Use this function to display the device name It can also be found on the nameplate Additional information Read access Operator Write access Order code Navigation Diagnostics De...

Страница 245: ...escription Display the three parts of the extended order code User interface Character string comprising numbers letters and special characters 20 Additional information Read access Operator Write access Service The extended order code indicates the selected option of all ordering features and thus uniquely identifies the device ...

Страница 246: ...mation Read access Operator Write access Maintenance Diagnostic event simulation Navigation Diagnostics Simulation Diag event sim Description Select a diagnostic event to simulate this event Selection The diagnostic events of the device Factory setting Off Additional information Read access Operator Write access Maintenance To terminate the simulation select Off Simulation distance on Navigation D...

Страница 247: ...al information Read access Operator Write access Maintenance Current output N simulation Navigation Diagnostics Simulation Curr outp N sim Prerequisite The device has an Anlog I O module Operating mode 138 4 20mA output or HART slave 4 20mA output Description Switches the simulation of the current on or off Selection Off On Factory setting Off Additional information Read access Operator Write acce...

Страница 248: ...ating menu Micropilot NMR84 248 Endress Hauser User entry 3 4 to 23 mA Factory setting The current at the time the simulation was started Additional information Read access Operator Write access Maintenance ...

Страница 249: ...check Result dev check Description Shows the overall result of the device check Additional information Read access Operator Write access The device has a function that detects and reports any interference by unfavorable installation situation Here the amplitudes of measured signals are monitored which refer to interference in the near range Level signal Navigation Diagnostics Device check Level si...

Страница 250: ...user Near distance Navigation Diagnostics Device check Near distance Prerequisite Only visible after a device check Description Shows the result of the device check for the near distance area Additional information Read access Operator Write access ...

Страница 251: ...ariant Parameter 157 Communication status Parameter 127 Configuration Submenu 154 157 161 164 Confirm distance Parameter 120 Contact type Parameter 150 Contrast display Parameter 228 Covered tank Parameter 196 CTSh Submenu 196 CTSh correction value Parameter 196 CTSh mode Parameter 196 Current output N simulation Parameter 247 Current span Parameter 139 D Damping factor Parameter 137 146 217 Date ...

Страница 252: ...r Parameter 227 Header text Parameter 227 HH alarm Parameter 214 HH alarm value Parameter 213 HH H alarm Parameter 215 History reset Parameter 222 Hour Parameter 234 HTMS Submenu 201 HTMS mode Parameter 201 Hysteresis Parameter 203 HyTD Submenu 191 HyTD correction value Parameter 191 HyTD mode Parameter 191 I Information Submenu 172 220 Input value Parameter 135 142 150 Input value Parameter 143 I...

Страница 253: ...sent mapping Parameter 122 Pressure Submenu 115 184 Pressure unit Parameter 231 Previous diagnostics Parameter 239 Primary variable PV Parameter 167 Probe position Parameter 136 Process value Parameter 134 145 Process variable Parameter 134 144 Product safety 8 PV mA selector Parameter 166 PV source Parameter 164 Q Quaternary variable QV Parameter 171 R Readback value Parameter 151 Recalibration 9...

Страница 254: ...ank ullage Parameter 110 Temperature Submenu 111 178 Temperature unit Parameter 231 Tertiary variable TV Parameter 169 Thermocouple type Parameter 133 Timestamp Parameter 239 240 Timestamp 1 to 5 Parameter 242 Trouble shooting 81 Tube diameter Parameter 119 220 U Units preset Parameter 118 230 Upper interface level Parameter 110 Used for SIL WHG Parameter 146 152 User role Parameter 124 V V1 addre...

Страница 255: ......