E L C P r o g r a m m i n g M a n u a l
F or mo re inf or ma tio n visi t: www.eato n.co m MN 05 0 03 0 03 E
A -20
Field Name
ASCII
Command code
0F
Register T0 Address Hi
05
Register T0 Address Lo
00
Preset Data Hi
00
Preset Data Lo
0A
Error Check ( LRC )
E1
END 1
0D (Hex)
END 0
0A (Hex)
Command Code
:
16, Write Multiple Register
What is the maximum number of registers supported?
Example: Set register T0 to 00 0A, T1 to 01 02.
Master
→
ELC “: 01 10 06 00 00 02 04 00 0A 01 02 C6 CR LF”
Sent message:
Field Name
ASCII
Heading 3A
(Hex)
Slave Address
01
Command code
10
Starting Address Hi
06
Starting Address Lo
00
Number of Register Hi
00
Number of Register Lo
02
Byte Count
04
Data Hi
00
Data Lo
0A
Data Hi
01
Data Lo
02
Error Check (LRC)
C6
END 1
0D (Hex)
END 0
0A (Hex)
ELC
→
Master “: 01 10 06 00 00 02 E7 CR LF”
Feedback message:
Field Name
ASCII
Heading 3A
(Hex)
Slave Address
01
Command code
10