E L C P r o g r a m m i n g M a n u a l
F o r
m o r e
i n f o r m a t i o n v i s i t :
w w w. e a t o n . c o m
M N 0 5 0 0 3 0 0 3 E
3 - 3 9 8
word) for CH2 (Y4, Y5).
- The 32-bit data stored in the present value registers D1378 (high word) and D1377 (low
word) for CH3 (Y5, Y6).
10. When in the reverse direction, the contents of the present value register will decrease.
11. For the ELC-PH series, the number of pulses will be stored in the current value register
(D1349 high byte, D1348 low byte) for CH0 (Y10), or current value register (D1351 high byte,
D1350 low byte) for CH1 (Y11). When the rotation direction is negative, the contents of the
current value register will decrease.
12. For the ELC-PV series, when the DRVA instruction is sending pulses, you cannot change the
operands. The changes will not be valid until the next time the instruction is enabled.
13. For the ELC-PV series, when the conditions preceding the DRVA instruction are OFF, the
pulse output will decelerate to a stop and M1029 and M1030 will turn ON. For the ELC-PH
series, if the conditions preceding the DRVA instruction turn OFF while the instruction is
executing, the machine will decelerate and stop and the execution completed flag M1102,
M1103 will turn ON.
14. For the ELC-PV series, when the conditions preceding the DRVA instruction are OFF, and the
flag M1336 for the CH0 pulses or M1337 for the CH1 pulses are “ON”, the DRVA instruction
will not execute.
15. When the absolute value of the input frequency of DRVA and DDRVA instructions in the
ELC-PV series is greater than 200KHz, the output will be at 200KHz. When the absolute value
of the input frequency is less than 10Hz, the output will be at 10Hz.
16. D1343 (D1353) is the acceleration/deceleartion time of the first step acceleration and the last
step deceleration. The acceleration and deceleration time of the ELC-PV series shall not be
shorter than 10ms. The output will be set to 10ms if the time is shorter than 10ms and set to
100ms if the time is longer than 10,000ms. For the ELC-PH series, the setting range is
50~20,000 ms. If the setting greater than / less than 20,000 ms / 50 ms, 20,000 ms / 50 ms will
be used.
17. For the ELC-PV series, M1305 (M1306) is the direction signal for CH0 (CH1). When
S
1
is a
positive number, the output will be operated in a forward direction and M1305 (M1306) will be
OFF. When
S
1
is a negative number, the output will be operated in the reverse direction and
M1305 (M1306) will be ON.
18. For the ELC-PH series, D1340 (D1352) is the start/end frequency setting of Y10 (Y11). If the
pulse output frequency
S
2)
is less than or equal to the start/end frequency, the start/end
frequency will be the pulse output frequency.
19. Flags: Refer to API 158 DRVI for information on M1010, M1102, M1103, M1334, M1335,
M1336, M1337, M1346
Содержание ELC-PB
Страница 1: ......
Страница 5: ...For more information visit www eaton com MN05003003E iv...
Страница 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Страница 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Страница 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Страница 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...