3 . I n s t r u c t i o n S e t
M N050 03003E F or mo re infor ma tio n vi sit:
w w w. e a t o n . c o m
3-103
API Mnemonic
Function
47
ANR P
Alarm Reset
OP Range
Program
Steps
N/A Instruction driven by contact is necessary.
ANR, ANRP: 1 steps
ELC ELCB
ELCM
PB PC/PA/PH
PV
PB PH/PA
32 16
P
32 16
P
32 16
P 32 16 P 32 16
P
Description:
1.
ANR instruction is used to reset an alarm.
2.
When several alarm devices are ON, the lowest alarm number will be reset.
3.
This instruction works best with the pulse instruction (ANRP).
Program Example:
1.
When X20 and X21 are simultaneously ON more than 2 seconds, the alarm S910 = ON. If
X20 or X21 change to OFF, alarm S910 will remain ON. T10 will reset to OFF, present value
is 0.
2.
When X20 and X21 are simultaneously ON less than 2 seconds, the present value of T10 is
reset to 0.
3.
When X3 goes from OFF
→
ON, activated alarms S896~S1023 (ELC-PC/PA/PH) or
S900~S1023 (ELC-PV) or S912~S1023 (ELCM-PH/PA) will be reset.
4.
When X3 goes from OFF
→
ON again, the second lowest alarm number will be reset.
X20
ANS
T10
K20
S910
X21
X3
ANRP
Points to note:
Flags:
1.
M1048: When M1049 = ON, any alarm S896~S1023 (ELC-PC/PA/PH) =ON or S900~S1023
(ELC-PV) =ON or S912~S1023 (ELCM-PH/PA) =ON will turn M1048 ON. If M1049=OFF,
M1048 will not be affected if alarms occur.
2.
M1049: When M1049 = ON, D1049 will automatically hold the lowest alarm number during
the execution of this instruction.
Содержание ELC-PB
Страница 1: ......
Страница 5: ...For more information visit www eaton com MN05003003E iv...
Страница 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Страница 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Страница 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Страница 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...