2. Prog rammi ng Con cep ts
M N050 03003E F or m ore info rm ati on vi sit:
www.eaton.co m
2-21
SM
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
-PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
M1024 COM1 monitor request
Y Y
Y Y
OFF
- - R NO OFF
M1025
If the ELC receives an illegal
communication request when HHP, PC or
HMI connects to an ELC, M1025 =ON
and save the error code in D1025.
Y Y
Y Y
OFF
- - R NO OFF
M1026 Startup flag of RAMP module
- Y
Y Y
OFF
- -
R/W
NO OFF
M1027 PR output flag
- Y
Y Y
OFF
- -
R/W
NO OFF
M1028
10ms time switch flag. The base setting
flag of T64~T126 is 100ms, when timer is
OFF and the base setting flag is 10ms
when it is ON.
Y - Y -
OFF
- -
R/W
NO OFF
Pulse output Y0 of PLSY and PLSR
instruction execution completed or other
relative instruction execution completed
Y Y
- -
M1029
The 1st group pulse output CH0 (Y0, Y1)
is completed, or other relevant
instructions complete their executions.
- - Y Y
OFF
- - R NO OFF
Pulse output Y1 of PLSY and PLSR
instruction execution completed
Y Y
Y -
M1030 The 2nd group pulse output CH1 (Y2,
Y3) is completed, or other relevant
instructions complete their executions.
- - - Y
OFF
- - R NO OFF
M1031 Clear all non-latched memory
Y Y
Y Y
OFF
- -
R/W NO OFF
M1032 Clear all latched memory
Y Y
Y Y
OFF
- -
R/W NO OFF
M1033 Memory latched at STOP
Y Y
Y Y
OFF
- -
R/W NO OFF
M1034 All Y outputs disable
Y Y
Y Y
OFF
- -
R/W NO OFF
M1035
Start X input point to be RUN/STOP
switch and correspond to D1035 (ELC-
PC/ELCM-PH/ PA controllers indicate X7
only. ELC-PA controllers indicate X3 only.
ELC-PH controllers indicate X5 only.)
- Y
Y Y
- - -
R/W
YES OFF
ELC-PH VERSION 1.4 and above: SPD
instruction can use X0~X5 to detect
speed starting flag
- Y
- -
OFF OFF
- R/W NO OFF
M1036
The 3
rd
group pulse output CH2 (Y4, Y5)
is completed.
- - - Y
OFF
- - R NO OFF
M1037
The 4
th
group pulse output CH3 (Y6, Y7)
is completed.
- - - Y
OFF
- - R NO OFF
M1038
Switching T200~T255 timer resolution
(10ms/1ms). ON = 1ms.
- - Y -
OFF
- -
R/W
NO OFF
M1039 Constant scan mode
Y Y
Y Y
OFF
- -
R/W NO OFF
M1040 Step transition inhibit
Y Y
Y Y
OFF
- -
R/W NO OFF
M1041 Step transition start
Y Y
Y Y
OFF
- OFF
R/W NO OFF
M1042 Start pulse
Y Y
Y Y
OFF
- -
R/W NO OFF
Содержание ELC-PB
Страница 1: ......
Страница 5: ...For more information visit www eaton com MN05003003E iv...
Страница 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Страница 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Страница 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Страница 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...