API Mnemonic
Operands
Function
112
D MOVR P
S, D
Floating Point Data Move
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K
H KnX
KnY
KnM KnS T
C
D
E
F
S
D
*
*
*
*
*
*
DMOVR, DMOVRP: 9
steps
ELC ELCB
ELCM
PB PC/PA/PH
PV
PB PH/PA
32
16
P
32
16
P
32
16
P
32
16
P
32 16
P
Operands:
S
: Data source of the floating point value
D
: Destination of the move
Description:
1.
Directly enter a floating point value in
S
.
2.
When instruction is enabled, the contents of
S is moved
to
D
.
Program Example:
When X0 = OFF, D10 and D11 will not change. When X0 = ON, move F1.200E+0 (Input F1.2, and
scientific notation F1.200E+0 to D11/D10. In ELCSoft, under “Edit Monitored Devices” enter D10
and D11 and view the floating point data value for those addresses in the floating point column. ..
X0
DMOVR F1.200E+0
D10
Remarks:
DMOVR is a new instruction for V1.2 or later ELC-PB and ELCB-PB series controllers and for V1.2
of ELC-PC/PA/PH series controllers.
Содержание ELC-PB
Страница 1: ......
Страница 5: ...For more information visit www eaton com MN05003003E iv...
Страница 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Страница 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Страница 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Страница 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...