3 . I n s t r u c t i o n S e t
M N 0 5 0 0 3 0 0 3 E F or m o r e i nf o r m a t i o n v i s i t : www. e a t o n. c o m
3-487
Freq.
Time
2kHz
t2=11kHz
20ms
g2=40ms
20ms 20ms
1kHz
2kHz
t1=6kHz
3
rd
shift:
Assume t3 = 3kHz, gap frequency = 2kHz, gap time = 20ms
Ramp-down steps of 3
rd
shift:
Freq.
Time
Change to
t3
2kHz
t3=3kHz
t2=11kHz
Start to change
g3=60ms
20ms
20ms 20ms 20ms
For program examples please refer to API 199
Points to note:
Flag explanations:
M1029: CH0 (Y0, Y1) pulse output execution complete
M1102: CH1 (Y2, Y3) pulse output execution complete
M1078: Y0 pulse output pause (immediate)
M1104: Y2 pulse output pause (immediate)
M1305: Reverse Y1 pulse output direction for the high speed pulse output instructions
M1306: Reverse Y3 pulse output direction for the high speed pulse output instructions
M1538: Indicating pause status of Y0
M1540: Indicating pause status of Y2
Special register descriptions:
D1030: Low word of the present value of Y0 pulse output