E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-150
5.
For the pulse output terminal specified in D, the ELC-PV series can use Y0, Y2, Y4 and Y6,
The ELC-PB/PC/PA, ELCB-PB series can use Y0 and Y1 and the ELC-PH series can use Y0,
Y1, Y10 and Y11. (ELC-PH V1.2 and above supports Y10 and Y11).
6.
The ELC-PV series has four groups of A-B phase pulse outputs from CH0 (Y0, Y1), CH1 (Y2,
Y3), CH2 (Y4, Y5) and CH3 (Y6, Y7). See the remarks in section 2.3 concerning how to set
this up. .
7.
When the PLSY instruction has been executed, the specified quantity of pulses
S
2
will be sent
out the output terminal specified by
D
at the specified pulse output frequency
S
1
.
8.
When the PLSY instruction is used in a program, the outputs used in the PLSY instruction
cannot be used in the PWM instruction or PLSR instruction.
9.
Pulse output complete flags for each controller type:
ELC
ELC-PB/PC/PA/PH
ELCB-PB
ELC-PH
ELC-PV
Output device
Y0
Y1
Y10
Y11
Y0
Y2
Y4
Y6
Flag M1029
M1030
M1102 M1103 M1029 M1030 M1036
M1037
a) For ELC-PB/PC/PA/PH, ELCB-PB series, after the Y0 pulse output is complete, M1029 =
ON; after the Y1 pulse output is complete, M1030 = ON. When the PLSY instruction is
OFF, M1029 and M1030 will be OFF.
b) The execution complete flags M1029, M1030 should be cleared by the user after the
execution of the instruction has been completed.
c) For the ELC-PH series, M1102 is set to ON after Y10 finishes sending the specified
number of pulses and M1103 is set to ON after Y11 finishes sending the specified number
of pulses. When the PLSY instruction is OFF, M1102 and M1103 will be OFF.
d) For ELC-PV series, M1029 is set to ON after Y0 finishes sending the specified number of
pulses , M1030 is set to ON after Y2 finishes sending the specified number of pulses,
M1036 is set to ON after Y4 finishes sending the specified number of pulses, and M1037
is set to ON after Y6 finishes sending the specified number of pulses. When the PLSY
instruction is OFF, M1029, M1030, M1036, and M1037 will not be turned OFF
automatically. The user program will need to reset them.
10. For the ELC-PB/PC/PA/PH, ELCB-PB series controllers, when the PLSY and DPLSY
instructions are disabled, the pulse output completed flags will all be turned Off automatically.
11. For the ELC-PV series, when the PLSY and DPLSY instructions are disabled, the user will
have to reset the pulse output complete flags. They are not reset automatically like with the
other ELC controllers.
12. While the PLSY instruction is being executed, the output will not be affected if
S
2
is changed.
To change the number of output pulses, the PLSY instruction must be disabled, then change
the number the number of pulses.
Содержание ELC-PB
Страница 1: ......
Страница 5: ...For more information visit www eaton com MN05003003E iv...
Страница 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Страница 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Страница 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Страница 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...