Points to note:
1.
Bit addresses Y, M, S and word addresses T, C, D, can be reset individually with the RST
instruction.
2.
For clearing multiple devices, API 16 FMOV instruction can be used to send K0 to word
addresses T, C, D or bit addresses KnY, KnM, KnS.
RST
M0
X0
RST
T0
RST
Y0
FMOV
K0
D10
K5