[80]
SL digital output A
See
parameter 13-52 SL Controller Action
. The input goes high whenever the smart logic action
[38] Set dig. out. A high
is executed. The input goes low whenever the smart logic
[32] Action Set
dig. out. A low
is executed.
[81]
SL digital output B
See
parameter 13-52 SL Controller Action
. The input goes high whenever the smart logic action
[39] Set dig. out. B high
is executed. The input goes low whenever the smart logic
[33] Action Set
dig. out. B low
is executed.
[82]
SL digital output C
See
parameter 13-52 SL Controller Action
. The input goes high whenever the smart logic action
[40] Set dig. out. C high
is executed. The input goes low whenever the smart logic
[34] Action Set
dig. out. C low
is executed.
[83]
SL digital output D
See
parameter 13-52 SL Controller Action
. The input goes high whenever the smart logic action
[41] Set dig. out. D high
is executed. The input goes low whenever the smart logic
[35] Action Set
dig. out. D low
is executed.
[97]
Check Valve Monitor
A check valve monitor condition has been detected. Enable the function in
parameter 22-04
Check Valve Monitor
.
[160] No alarm
The output is high when no alarm is present.
[161] Running reverse
The output is high when the drive is running counterclockwise (the logical product of the status
bits running and reverse).
[165] Local ref. active
The output is high when local reference is activated by the [Hand On] key on the LCP or by hand-
on command of digital input.
[166] Remote ref. active
The output is high when remote reference is activated by the [Auto On] key on the LCP or by
auto-on command of digital input.
[167] Start command activ
The output is high when there is an active start command (that is, via digital input bus connec-
tion or [Hand On] or [Auto On], and no stop command is active.
[168] Drive in hand mode
The output is high when the drive is in hand-on mode (as indicated by the LED light above
[Hand On]).
[169] Drive in auto mode
The output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto
On]).
[188] AHF Capacitor Con-
nect
Connect or disconnect AHF capacitor.
[190] No-Flow
A no-flow condition has been detected. See
parameter group 22-2* No-Flow Detection
.
[191] Dry Pump
A dry-pump condition has been detected. Enable the function in
parameter 22-26 Dry Pump
Function
.
[192] End Of Curve
An end-of-curve condition has been detected. Enable the function in
parameter 22-50 End of
Curve Function
.
[193] Sleep Mode
The drive/system has entered sleep mode. See
parameter group 22-4* Sleep Mode
.
[194] Broken Belt Function
A broken-belt condition has been detected. Enable the function in
parameter 22-60 Broken Belt
Function
.
[196] Fire Mode
The drive is operating in fire mode. See
parameter group 24-0* Fire Mode
.
[198] Drive Bypass
To be used as a signal for activating an external electromechanical bypass, switching the motor
directly on line. See
parameter group 24-1* Drive Bypass
.
[211] Cascade Pump 1
Cascade pump 1 is running.
[212] Cascade Pump 2
Cascade pump 2 is running.
AU363928304090en-000101 / 130R0982
88 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111