Table 93: Option:
[0]
Off
The brake resistor is not active.
[2]
AC brake
AC brake is active.
2-16 AC Brake, Max current
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
Enter the maximum permissible current when using the AC brake to avoid overheating motor windings.
Table 94: Range:
Min: 0%
Max: 160%
Default value: 100%
2-17 Over-voltage Control
Default value: [2] Enabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select whether to enable OVC during ramp down, which reduces the risk of drive trip due to overvoltage on the DC link caused by
generative power from load.
Table 95: Option:
[0]
Disabled
No OVC required.
[1]
Enabled (not at stop)
Activates OVC when the drive is not in the stop state.
[2]
Enabled
Activates OVC.
N O T I C E
The ramp time is automatically adjusted to avoid tripping of the drive.
2-19 Over-voltage Gain
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
This parameter enables the user to fine tune the overvoltage gain for
parameter 2-17 Over-voltage Control
. It is not necessary to
change this parameter for normal applications.
Table 96: Range:
Min: 1%
Max: 500%
Default value: 100%
4.5 Parameter Group 3-** Reference/Ramps
4.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits, and ranges. Also see
parameter group 20-0* Feedback
for information on settings in
closed loop.
3-02 Minimum Reference
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: int32
Change during operation: True
AU363928304090en-000101 / 130R0982 | 59
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide