Table 258: Option:
[0]
Disabled
[1]
Warning
[2]
Trip
14-55 Output Filter
Default value: [0] No filter
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Select the type of connected output filter.
Table 259: Option:
[0]
No filter
No filter is selected.
[1]
Sine-wave filter
For backwards compatibility only.
[3]
Sine-wave filter with feedback
Sine wave filter with feedback is selected.
[4]
dv/dt
This option is only valid for drives of the following enclosure sizes:
IP20, 3x380–480 V, enclosure sizes H6–H8.
4.11.7 14-6* Auto Derate
Parameter group for configuring automatic derating based on the output frequency of the drive.
14-61 Function at Inverter Overload
Default value: [0] Trip
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
When the drive issues an inverter overload warning, select whether to continue and probably trip the drive or derate the output
current.
Table 260: Option:
[0]
Trip
[1]
Derate
14-63 Min Switch Frequency
Default value: [2] 2.0 kHz
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Set the lowest switch frequency allowed by the application.
Table 261: Option:
[2]
2.0 kHz
[3]
3.0 kHz
[4]
4.0 kHz
[5]
5.0 kHz
[6]
6.0 kHz
[7]
8.0 kHz
AU363928304090en-000101 / 130R0982 | 137
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide