N O T I C E
Do not set
parameter 14-20 Reset Mode
to
[13] Infinite auto reset
, when
parameter 22-60 Broken Belt Function
is set to
[2] Trip
. Doing
so causes the drive to continuously cycle between running and stopping when a broken-belt condition is detected.
N O T I C E
If the automatic bypass function is enabled, the bypass starts when the drive experiences a persistent alarm condition. In this
case, disable the automatic bypass function if
[2] Trip
is selected as the broken-belt function.
Table 406: Option:
[0] Off
This function is not active.
[1] Warning The drive continues to run, but activates a broken-belt warning (
warning 95, Broken Belt
). A drive digital output or
a serial communication bus can communicate the warning to other equipment.
[2] Trip
The drive stops running and activates a broken-belt alarm (
alarm 95, Broken Belt
). A drive digital output or a serial
communication bus can communicate the alarm to other equipment.
22-61 Broken Belt Torque
Default value: 10%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: True
Set the broken-belt torque as a percentage of the rated motor torque.
Table 407: Range:
Min: 5%
Max: 100%
Default value: 10%
22-62 Broken Belt Delay
Default value: 10 s
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
Set the time for which the broken-belt conditions must be active before carrying out the action selected in
parameter 22-60 Broken
Belt Function
.
Table 408: Range:
Min: 0 s
Max: 600 s
Default value: 10 s
4.16.7 22-8* Flow Compensation
In certain applications, it is not possible for a pressure transducer to be placed at a remote point in the system, and it can only be
placed close to the fan/pump outlet. Flow compensation operates by adjusting the setpoint according to the output frequency,
which is almost proportional to flow. Thus, it compensates for higher losses at higher flow rates.
H
DESIGN
(required pressure) is the setpoint for closed-loop (PI) operation of the drive and is set as for closed-loop operation without
flow compensation.