Table 240: Option:
[0]
Trip
Trip the drive.
[1]
Warning
Issues a warning.
[2]
Disabled
No action.
[3]
Derate
The drive would derate.
14-15 Kin. Back-up Trip Recovery Level
Default value: 200.000 ReferenceFeedbackUnit
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: u_int32
Change during operation: True
Enter the kinetic back-up trip recovery level for the application. This recovery level is the minimum speed of the motor at which the
drive is to ramp up the speed.
Table 241: Range:
Min: 0
Max: 60000.000 ReferenceFeedbackUnit
Default value: 200.000 ReferenceFeedbackUnit
4.11.3 14-2* Reset Functions
Parameters for configuring auto reset handling, special trip handling and control card self-test or initialization.
14-20 Reset Mode
Default value: [0] Manual reset
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Define whether the drive waits for a manual reset, or resets itself automatically after tripping. In manual reset mode, press [RESET] or
use digital inputs to reset the drive.
N O T I C E
In automatic reset mode, the motor can start without a warning.
Table 242: Option:
[0]
Manual reset
Select
[0] Manual reset
to reset the drive via [Reset] or via the digital inputs.
[1]
Automatic reset x 1
Select
[1]-[12] Automatic reset x 1… x20
to perform between 1 and 20 automatic resets after trip-
ping.
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10