N O T I C E
If no run permissive signal is applied but either run, jog, or freeze commands is activated, the status
line in the display shows either
Run Requested
,
Jog Requested
, or
Freeze Requested
.
[53]
Hand start
A signal applied puts the drive into hand-on mode as if [Hand On] is pressed and a normal stop com-
mand is overridden. If the signal is disconnected, the motor stops. To make any other start commands
valid, assign another digital input to
Auto Start
and apply a signal. The [Hand On] and [Auto On] keys
have no impact. The [Off] key overrides
Hand Start
and
Auto Start
. Press either [Hand On] or [Auto On]
to reactivate
Hand Start
and
Auto Start
. If there is no signal on
Hand Start
or
Auto Start
, the motor stops
regardless of any normal start command applied. If a signal is applied to both
Hand Start
and
Auto
Start
, the function is
Auto Start
.
[54]
Auto start
A signal applied puts the drive into auto-on mode as if [Auto On] is pressed. See also
[53] Hand Start
.
[60]
Counter A (up)
Input for increment counting in the SLC counter.
[61]
Counter A
(down)
Input for decrement counting in the SLC counter.
[62]
Reset Counter
A
Input for reset of counter A.
[63]
Counter B (up)
Input for increment counting in the SLC counter.
[64]
Counter B
(down)
Input for decrement counting in the SLC counter.
[65]
Reset Counter B Input for reset of counter B.
[101] Sleep
A signal applied puts the drive into sleep mode.
[120] Lead Pump
Start
A signal applied puts the lead pump into start mode.
[121] Lead Pump Al-
ternation
A signal applied puts the lead pump into alternation mode.
[130] Pump 1 Inter-
lock
A signal applied puts pump 1 into interlock mode.
[131] Pump 2 Inter-
lock
A signal applied puts pump 2 into interlock mode.
[132] Pump 3 Inter-
lock
A signal applied puts pump 3 into interlock mode.
[133] Pump 4 Inter-
lock
A signal applied puts pump 4 into interlock mode.
[134] Pump 5 Inter-
lock
A signal applied puts pump 5 into interlock mode.
[190] Fire Mode Ref
Bit 0
Enable a selection of 1 of the 8 fire mode references according to
.
[191] Fire Mode Ref
Bit 1
Enable a selection of 1 of the 8 fire mode references according to
.
[192] Fire Mode Ref
Bit 2
Enable a selection of 1 of the 8 fire mode references according to
.
AU363928304090en-000101 / 130R0982
74 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide