Table 348: Range:
Min: 0
Max: 4294967295
Default value: 0
4.14 Parameter Group 18-** Info & Readouts
Parameter group for drive information and data readouts.
4.14.1 18-1* Fire Mode Log
View up to 10 latest faults, that have been suppressed during Fire Mode. [0] is the most recent logged data, and [9] the oldest. Error
codes, values, and time stamp can be viewed for all logged data.
18-10 FireMode Log:Event
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: True
View fire mode event.
Table 349: Range:
Min: 0
Max: 255
Default value: 0
4.14.2 18-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
18-50 Sensorless Readout [unit]
Default value: 0 SensorlessUnit
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: int32
Change during operation: False
View the pressure or flow resulting from the sensorless calculations. This value is not the value used for control. The value is only
updated if sensorless data supports both flow and pressure.
Table 350: Range:
Min: -999999.999
Max: 999999.999 SensorlessUnit
Default value: 0 SensorlessUnit
4.14.3 18-8* Compatibility
18-87 Inv. Max. Current
Default value: 0.00 A
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int32
Change during operation: True
View the inverter maximum current. This data is used for calculation of drive protection and so on.
Table 351: Range:
Min: 0.00 A
Max: 9999.99 A
Default value: 0.00 A
18-88 Motor current
Default value: 0.00 A
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int32
Change during operation: True
View the motor current measured as a mean value I
rms
.
Table 352: Range:
Min: 0.00 A
Max: 9999.99 A
Default value: 0.00 A
AU363928304090en-000101 / 130R0982
156 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide