[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
Select
[13] Infinite Automatic Reset
for continuous resetting after tripping.
14-21 Automatic Restart Time
Default value: 10 s
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
To start the automatic reset function, enter the time interval from trip. This parameter is active when
parameter 14-20 Reset Mode
is
set to
[1] - [13] Automatic reset
.
N O T I C E
A value of 0 s cannot be set when
parameter 14-20 Reset Mode
is set to option
[13] Infinite auto reset
.
Table 243: Range:
Min: 0 s
Max: 600 s
Default value: 10 s
14-22 Operation Mode
Default value: [0] Normal operation
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To reset all parameter values to default, select
[2] Initialisation
.
Table 244: Option:
[0] Normal op-
eration
Select
[0] Normal operation
for normal operation of the drive with the motor in the selected application.
[2] Initialisation
Select
[2] Initialisation
to reset all parameter values to default settings, excluding bus communication param-
eters,
parameter group 15-0* Operating Data
, and
parameter group 15-3* Alarm Log
. The drive is reset during
the next power-up.
Parameter 14-22 Operation Mode
also reverts to the default setting
[0] Normal operation
.
14-23 Typecode Setting
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: False
Service use only.
Table 245: Range:
Min: 0
Max: 255
Default value: 0
14-27 Action At Inverter Fault
Default value: [1] Warning
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select how the drive acts in the case of overvoltage, overcurrent, short circuit, or grounding errors.
Table 246: Option:
[0]
Trip
Disable the protection filters and trip at the 1st fault.
[1]
Warning
Run the protection filters normally.
AU363928304090en-000101 / 130R0982 | 133
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide