[211]
Cascade pump 1
[212]
Cascade pump 2
[213]
Cascade pump 3
[214]
Cascade pump 4
[215]
Cascade pump 5
6-73 Terminal 45 Output Min Scale
Default value: 0%
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Scale for the minimum output (0 mA or 4 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full
range of the variable selected in
parameter 6-71 Terminal 45 Analog Output
.
Table 173: Range:
Min: 0%
Max: 200%
Default value: 0%
6-74 Terminal 45 Output Max Scale
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Scale for the maximum output (20 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full range of the
variable selected in
parameter 6-71 Terminal 45 Analog Output
.
Table 174: Range:
Min: 0%
Max: 200%
Default value: 100%
6-76 Terminal 45 Output Bus Control
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
Holds the level of analog output if controlled by bus.
Table 175: Range:
Min: 0
Max: 16384
Default value: 0
4.8.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital output terminal 42. Analog outputs are current outputs: 0/4–20 mA. Resolu-
tion on analog outputs is 12 bit. Analog output terminals can also be set up as digital output.
6-90 Terminal 42 Mode
Default value: [0] 0-20 mA
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Set terminal 45 to act as analog output or as digital output.
AU363928304090en-000101 / 130R0982 | 99
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide