24-08 Mul FM Preset Reference
Default value: 0%
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: int16
Change during operation: True
Enter the required multi preset reference/setpoint for firemode operation. For selecting dedicated references, select fire mode refer-
ence bit 0/1/2 [190], [191], or [192] for the corresponding digital inputs in
parameter group 5-1* Digital Inputs
.
Table 430: Range:
Min: -100%
Max: 100%
Default value: 0%
24-09 Fire Mode Alarm Handling
Default value: [1] Trip, crit. alarms
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
N O T I C E
Certain alarms can affect the lifetime of the drive. If 1 of these ignored alarms occurs while in fire mode, a log of the event is
stored in the fire mode log.
In fire mode log, the 10 latest events of alarms that affect warranty, fire mode activation, and fire mode deactivation are stored.
N O T I C E
The setting in
parameter 14-20 Reset Mode
is disregarded if fire mode is active (see
parameter group 24-0* Fire Mode
).
Table 431: Fire Mode Alarm Handling
Number
Description
Critical alarms
Warranty affecting alarms
4
Mains ph. loss
–
x
7
DC over volt
x
x
9
Inverter overloaded
–
x
13
Overcurrent
x
x
14
Ground fault
x
x
16
Short circuit
x
x
38
Internal fault
x
–
69
Power card temp
–
x
AU363928304090en-000101 / 130R0982 | 181
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide